1. General
1.1
Use
The sensors 0
LINE 10020033.xx are designed to measure ambient temperature
2
and transmit it wirelessly to a matched receiver. As the sensor is supplied by a
solar cell, it is maintenance-free. As soon as the change in temperature exceeds
+/-0.5°C, a signal is sent immediately. Moreover, the signal is retransmitted every
15 minutes.
Note: Read the operating manual carefully before initial use.
1.2 Guarantee terms
This operating manual is an integral part of the device and our guarantee terms. It
must always be delivered to the user. We reserve the right to modify the technical
design of these devices without warning. TRI0
and their quality checked by making use of the latest technologies and taking into
account the applicable national and international directives. If nevertheless a fault
arises, TRI0
SYS undertakes to remedy the default as follows, without prejudicing
2
the rights of the end customer that arise from the sales contract with his reseller:
If the event of exercising of a legitimate and regular right, TRI0
sole discretion, rectify the device fault or supply a fault-free device. Any claim
beyond this and all claims for consequential damages are excluded.
A legitimate fault exists if the device cannot be used at the time of delivery to the
end customer because of a design or manufacturing defect or if its practical use is
severely limited. The guarantee is void in cases of natural wear and tear, incorrect
use, incorrect connection, where the device has been repaired or external
influence. The period of guarantee is 24 months (from the date of invoicing).
French law applies to the regulation of guarantee rights.
1.3 Recycling of the device
In accordance with European Directive 2012/19 / EU on waste
electrical and electronic equipment and its implementation in
accordance with national laws, this logo means that devices must not
be thrown away with household waste. The hazardous substances
they are likely to contain can harm health and the environment. Have
these devices taken back by your distributor or use the selective
collection means made available by your municipality.
2. Safety
Observe the following points:
• The laws, standards and directives in force.
• Best practice at the time of installation
• The device operating manual.
• An operating manual can only give general instructions. They must be
interpreted in the context of a specific installation.
The device is intended solely for use conforming to its purpose. Any repairs or
modifications by the user are forbidden! Do not use with other devices the
operation of which could endanger people, animals or property.
3. Technical characteristics
General characteristics
Transmission frequency
Transmission power
EnOcean Equipment Profile
Measurement range
Measurement accuracy
Measurement resolution
Storage temperature
Illumination
Degree of protection
Installation altitude
Range in buildings
Masonry
20m, through 3 walls at most
Reinforced concrete
10m, through 1 wall/ceiling at most
Plasterboard / wood
30m, through 5 walls at most
Note: The signal strength between the transmitter and the receiver decreases as
the distance increases. Where there is a line of sight connection, the range is
approximately 30 m in corridors and 100 m in large workshops or halls. The range
can be increased with an 0
LINE repeater.
2
TOC1117NUbb_1020
EN
SYS products are manufactured
2
SYS, may at its
2
868.3 MHz
10 mW max.
A5-02-05
from 0°C to +40°C
+/-0.5°C from +15°C to +25°C
0.16°C
From -20°C to +60°C
>100 lux on average per day
IP 30 on its base
2000m max.
4. Installation et mise en service
The sensor is supplied on a base which as well as installation allows a learn
process to be performed close to the matched receiver by separating (using a
small screwdriver to depress the clips) the sensor from the base; the base
remaining in position.
Base clip
4.1 Installation instructions:
Never mount the sensor in a metallic casing or close to a largely metallic
object. Installation on the ground or close to the ground is not
recommended
· The sensor must be positioned so that air can circulate freely around it and
within an area representative of the temperature to be measured.
· Secure the base by gluing or screwing.
· Place the sensor on its base until it engages.
4.2 Initial use:
The devices are supplied in an operational state but will probably require
recharging, following storage of the radio sensors in the dark.
· Prior to first use, charge the sensor's power reserve using light with an
illuminance of at least 200 lux for 5 minutes or more.
· Ensure that averaged across the day, the mean illuminance is 100 lux/d.
· The sensor's operating power reserve (when fully charged) in conditions of
total darkness is 10 days. It is recommended not to let the sensor discharge
completely to avoid irreversible damage.
Note: The device is designed for interior use. Do not install it in locations that
could be sprayed by water! To clean, use a damp cloth!
5. Controls and functions
ion and initial use
10020033.xx sensors transmit the measured temperatures using the frame
described in the Enocean Equipment Profiles EEP2.1 document §A5-02-05
(consultable under www.enocean.com).
5.1 Temperature measurement:
The temperature is measured every 100 seconds. If the temperature change
between two measurements exceeds +/-0.5°C, a signal is sent.
If changes remain below this level, the temperature is transmitted approximately
every 15 minutes.
5.2 Programming and LRN button:
Located behind the sensor, pressing the
LRN button causes the sending of a frame
used to identify or associate a matched
receiver.
When the sensor is located on its base, it
must be first unclipped from the base to
access the LRN button and to place the
sensor closed to the matched receiver
during the identification or association phase (the receiver having reduced
sensitivity during this phase).
6. Troubleshooting
ion and initial use
6.1 New or existing installation
• If the receiver functions at a shorter distance relative to the sensor, it is subject
to interference or used outside the transmission range.
• Search the system environment for changes that could cause the interference
(for example movement of metallic cabinets, furniture or partitions).
• Use the sensor or receiver in a more suitable location.
• Clear the receiver and perform a new learn process.
6.2 Limitation of the range of the radio signals
• Transmitter/receiver used close to metallic objects or close to materials
containing metallic elements. Observe a distance of at least 10 cm.
• Humidity in the materials.
• Devices emitting high frequency signals such as audio and video systems,
computers, electronic ballasts or fluorescent tubes. Observe a distance of at
least 0.5 m.
6.3 Contacts
E-mail: ............................ contact@trio2sys.fr
7. Declaration of conformity
This product can be sold and operated in the countries of the European Union.
TRI0
SYS hereby declares that the receiver 10020033.xx complies with the
2
essential requirements and other relevant prescriptions of Directive
.
known as the RED Directive
For more details on the applied standards please consult website
78 mm
25 mm
LRN button
2014/53/EU,
www.trio2sys.fr
D. Girard
2/2