DB7110U Universal Heat Pump
Defrost Controller
APPLICATION
The DB7110U Universal Heat Pump Defrost
Controller is a heat pump defrost control used in
single stage heat pump appliances. This product
replaces over 260 OEM and competitive controls and
can be easily programmed to meet the requirements
of virtually any single stage heat pump. See Table 2,
"Compatibility Chart.," on page 5.
FEATURES
The DB7110U provides:
• Universal defrost control for single stage heat
pumps
• LED display for easy setup and configuration
• Small, square footprint for easier installation
• Demand and timed defrost modes
• System status and fault indication
• Selectable reversing delay to limit noise when
going in and out of a defrost cycle
• Fault history for easy troubleshooting
DB7110U-DEFROST CONTROL
SYSTEM
FAULT
Fig. 1. DB7110U1000.
MENU
SETTING
M37637
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
Electrical Ratings
Input Voltage: 24VAC, 60Hz
Max. Input Current: 200mA
Compressor Contactor: 1A @ 24VAC
Outdoor Fan:
1/2HP motor
5A full load, 30A locked rotor, 240VAC.
Aux Heat: 1A @ 24VAC
Reversing Valve: 1A @ 24VAC
All outputs rated for 100,000 operations.
All terminals except FAN-IN and FAN-OUT are NEC
Class 2 low voltage.
Environmental Ratings
Operating Temperature Range: -40F to 150F
Humidity Limits: less than 95% (non-condensing)
INSTALLATION AND
CONFIGURATION
Overview
When Installing This Product...
1. Read these instructions carefully. Failure to fol-
low instructions can damage the product or
cause a hazardous condition.
2. Check ratings given in these instructions and
on the product to make sure the product is suit-
able for your application.
3. Installer must be a trained, experienced service
technician.
4. Use these instructions to check out the product
operation after installation.
34-00032EF-01

Publicité

Table des Matières
loading

Sommaire des Matières pour Honeywell Home DB7110U

  • Page 1 DB7110U Universal Heat Pump Defrost Controller INSTALLATION INSTRUCTIONS APPLICATION SPECIFICATIONS The DB7110U Universal Heat Pump Defrost Electrical Ratings Controller is a heat pump defrost control used in single stage heat pump appliances. This product Input Voltage: 24VAC, 60Hz replaces over 260 OEM and competitive controls and can be easily programmed to meet the requirements Max.
  • Page 2: Control Location

    DB7110U. 2. Mount DB7110U inside the junction box on the outdoor unit using the two included self-drilling sheet metal screws. 3. Use the control as a template to drill new mount- ing holes if necessary.
  • Page 3 DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER Wiring OUTDOOR INDOOR DB7110U EQUIPMENT EQUIPMENT FAN-OUT WARNING FAN-IN Electrical Shock Hazard. Can cause severe injury, death, or property damage. REVERSING VALVE Disconnect power supply before beginning wiring to prevent electrical shock or equipment...
  • Page 4: Configuration

    2. On power up the display will briefly flash the software version of the DB7110U and then begin The DB7110U will remain in defrost for at least cycling between the normal operating screens one minute. After one minute has elapsed, the...
  • Page 5: Compatibility Chart

    DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER COMPATIBILITY CHART Table 2. Compatibility Chart. (Continued) Lennox 100269-01 100269-02 Table 2. Compatibility Chart. 100269-04 100269-05 Amana C64301-1 C6431001 11K7101 1507N170027 Arcoaire 32312-00 3232140 29M0101 29M0201 Armstrong 39840B001 44614-0001 30W87 33G9501 44614-002 46257-001 34M6301...
  • Page 6 DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER Table 2. Compatibility Chart. (Continued) Tempstar/ICP 1084-100 1084-83-1008 1087562 Therm-O Disc 26E-10 Trane 21C14501G18 21C1450127 21C1450136 21C1450137 21C1450138 21C1450142 21C1450144 21C1450145 21C1450153 21C1450154 21C1450155 21C1450160 21C14282G01 CNT01106 CNT01108 CNT01129 CNT01152 CNT01431 CNT01510 CNT01642 CNT01923...
  • Page 7: User Interface

    DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER USER INTERFACE The user interface consists of three buttons, two LED’s, and 4 7-segment digits. The two left digits generally represent the category of what is being displayed while the two right digits represent the value or setting of the category.
  • Page 8 DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER Table 4. Configuration Screens. (Continued) Display Description Range Default Reverse Delay 0-30 seconds 30 seconds Compressor off time when switching between heating and defrost modes. Setting this to 0 will shorten the overall defrost time, but may result in objectionably loud noises when entering/exiting defrost (depending on compressor type).
  • Page 9: Troubleshooting And Maintenance

    DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER TROUBLESHOOTING AND MAINTENANCE IMPORTANT Due to the potential hazard of line voltage, only a trained experienced service technician should perform the troubleshooting procedures. This control contains no field-serviceable parts. Do not attempt to take it apart. Replace the entire control if operation is not as described.
  • Page 10 DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER Table 5. Troubleshooting. (Continued) Condition Procedure Control Status Corrective Action System does not Observe operational Display shows COOL • O/b configured incorrectly. Verify defrost at all mode while heating. proper setting of O/b input for reversing valve control.
  • Page 11 DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER Table 6. Fault Code Information. Fault No. Description Corrective Action Internal Communication Fault • Replace control Internal Fault • Replace control Low 24V • Measure 24V (R & C). There may be something in the system loading the 24V transformer excessively.
  • Page 12 34-00032EF—01 M.S. 03-19 | Printed in United States This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-633-3991 ©2019 Resideo Technologies, Inc. The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved.
  • Page 13: Spécifications

    APPLICATION SPÉCIFICATIONS Le régulateur de dégivrage universel pour Spécifications électriques thermopompe DB7110U est utilisé avec les thermopompes à un étage. Ce produit remplace plus Tension d’entrée : 24 V c.a., 60 Hz de 260 régulateurs de fabricants d’origine et peut-être facilement programmé pour répondre aux Intensité...
  • Page 14: Emplacement Du Régulateur

    Sans réglage correct des températures d'activation et capteur de température d’air, le DB7110U de fin de cycle sur le DB7110U. Ils sont souvent ()dégivrera lorsque la température du serpentin marqués par leurs points d’ouverture et de est inférieure à...
  • Page 15 RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U 3. Ne placez pas le capteur de température d’air Function trop près du serpentin, car cela pourrait avoir LPC (2 bornes) Contacteur de basse pression – ces une incidence sur les lectures du capteur.
  • Page 16 RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U ÉQUIPEMENT ÉQUIPEMENT EXTÉRIEUR MODE DE FONCTIONNEMENT DB7110U INTÉRIEUR ACTUEL ARRÊT, CHAUFFAGE, VENTILATEUR FAN-OUT CLIMATISATION, RETARD, ETC. FAN-IN TEMPÉRATURE DU SERPENTIN ROBINET EXTÉRIEUR EN DEGRÉS INVERSEUR FAHRENHEIT CONTACTEUR COMPR HAUTE PRESSION TEMPÉRATURE DE L’AIR CONTACTEUR EXTÉRIEUR EN DEGRÉS...
  • Page 17 RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U TABLEAU DE Tableau 2. Tableau de compatibilité. (Suite) Interthem 6208800 COMPATIBILITÉ Lennox 100269-01 100269-02 Tableau 2. Tableau de compatibilité. 100269-04 100269-05 Amana C64301-1 C6431001 11K7101 1507N170027 Arcoaire 32312-00 3232140 29M0101 29M0201 Armstrong 39840B001...
  • Page 18 RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U Tableau 2. Tableau de compatibilité. (Suite) SnyderGeneral 1395-329 CEBD430524-04B Tempstar/ICP 1084-100 1084-83-1008 1087562 Therm-O Disc 26E-10 Trane 21C14501G18 21C1450127 21C1450136 21C1450137 21C1450138 21C1450142 21C1450144 21C1450145 21C1450153 21C1450154 21C1450155 21C1450160 21C14282G01 CNT01106 CNT01108 CNT01129...
  • Page 19: Interface Utilisateur

    RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U INTERFACE UTILISATEUR L’interface utilisateur comprend trois boutons, deux voyants DEL et 4 chiffres à 7 segments. Les deux chiffres de gauche représentent généralement la catégorie de ce qui est affiché, tandis que les deux chiffres de droite représentent la valeur ou le réglage de la catégorie.
  • Page 20 RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U Tableau 4. Écrans de configuration. (Suite) Affichage Description Plage Par défaut Délai d’inversion. Temps d’arrêt du compresseur lors de la 0 à 30 secondes 30 secondes commutation entre les modes de chauffage et de dégivrage.
  • Page 21: Dépannage Et Entretien

    RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U DÉPANNAGE ET ENTRETIEN IMPORTANT En raison du risque potentiel que pose la tension secteur, seul un technicien d’entretien d’expérience qualifié peut effectuer les procédures de dépannage. Ce régulateur ne contient aucune pièce réparable sur le terrain. N’essayez pas de le démonter. Remplacez la totalité...
  • Page 22 RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U Tableau 5. Dépannage. (Suite) Condition Procédure État du régulateur Mesure corrective Le système Vérifiez la Le régulateur affiche la • O signifie que le régulateur sera en fonctionne dans configuration O/B. configuration actuelle : mode de CLIMATISATION lorsqu’il y a...
  • Page 23 RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U Tableau 5. Dépannage. (Suite) Condition Procédure État du régulateur Mesure corrective Le système Observez le cycle de Le dégivrage se déclenche • Confirmez le bon positionnement du dégivre trop. dégivrage. trop souvent, même avec capteur et l’exactitude des lectures.
  • Page 24 34-00032EF—01 M.S. 03-19 | Imprimé aux États-Unis Ce produit est fabriqué par Resideo Technologies, Inc., Golden Valley, MN, 1-800-633-3991 ©2019 Resideo Technologies, Inc. La marque de commerce Honeywell Home est utilisée sous licence avec l’autorisation d’Honeywell International Inc. Tous droits réservés.

Table des Matières