#46443 User Guide
HeatLink
Electronic Thermostat
®
Modes Description
• Electronic thermostat with night setback mode for hydronic floor heating systems
controlled by actuators.
• External pilot wire for night setback, equipped with a switch to select heating,
manual setback or timer setback mode.
• Regulating on internal sensor.
• Option: Possibility to regulate with an external sensor (NTC 10K)
The external sensor must be connected without a power supply. At power up
the thermostat automatically detects the sensor used. (If the external sensor is
connected the thermostat will use this sensor)
• Silent (triac output), to be connected directly to actuators (see connecting drawing
on the installation sheet) or to the StatLink
StatLink
module datasheet)
®
L646443 - September 14, 2006
HeatLink and StatLink are registered trademark of HeatLink Group Inc.
Optional external sensor
(sold separately)
®
system. (In this case please refer to the
Screw connector for power supply,
output and clock (pilot wire)
LED Indicator
Green:
Heating indication with internal sensor regulation
Green blinking: Heating indication with external sensor regulation
Orange:
Reduction mode by clock (pilot wire)
Red:
internal sensor failure
Red blinking:
external sensor failure
Technical Characteristics
Measured temperature precision
Operating temperature
Setting temperature range
Regulation characteristics
Electrical protection
Power supply
Output
Optional external floor sensor
LED Indicator
Select mode
Room setting
Screw connector for internal
or external sensor
0.1°C (or 0.2°F)
0°C - 50°C (or 32°F – 122°F)
5°C - 30°C
(or 41°F - 86°F)
Static differential 0.5°K
Class II - IP30
24 VAC +/- 10%
TRIAC output 24 VAC, 15 W max.
( 4 actuators)
NTC (10K Ohms)

Publicité

loading

Sommaire des Matières pour HeatLink 46443

  • Page 1 Class II - IP30 Power supply 24 VAC +/- 10% TRIAC output 24 VAC, 15 W max. Output ( 4 actuators) L646443 - September 14, 2006 Optional external floor sensor NTC (10K Ohms) HeatLink and StatLink are registered trademark of HeatLink Group Inc.
  • Page 2 Protection Class II - IP30 Alimentation 24 VAC +/- 10% TRIAC output 24 VAC, 15 W max. Sortie (4 servocommandes) L646443 - 14 septembre 2006 Capteur externe CTN 10K HeatLink et StatLink sont des marques déposées de HeatLink Group Inc.
  • Page 3 Limitation Limitación Limitation Max 25°C Min < x < Max Min 15°C 20°C 15°C 15°C 20°C 10°C 25°C 10°C 25°C Min 15°C Min 15°C Max 25°C Calibration Calibración Calibration 15 min 23°C...
  • Page 4 Installation Installation Instalación ~150 cm (60") min 20 cm (8") 60mm 31mm 80mm Color coding based on fire alarm cable (FAS105) Codage de couleur basé sur le câble d’alarme (FAS105) Codificación de color basada en el cable la alarma de incendio (FAS105) PPL IMP 3008 L646443...