Corrective Action - Little Giant VCC-20S Serie Manuel Du Propriétaire

Masquer les pouces Voir aussi pour VCC-20S Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Troubleshooting
Problem
Pump is not connected to electrical power.
Circuit breaker off or fuse removed.
Accumulation of debris or build-up on float. Clean float; a dirty float could be too heavy to operate correctly.
Pump does not start when
tank is full of condensate
Float movement obstruction.
water.
Defective switch.
Defective motor.
Pump is not connected to electrical power.
Liquid inflow matches or exceeds pump
output capacity.
Condensate is overflowing
Pump is not level.
from the tank.
Accumulation of debris or build-up on float. Clean float. A dirty float could be too heavy to operate correctly.
Check valve stuck or plugged
Outlet flow is blocked.
Pump impeller is not turning.
Defective switch.
Defective motor.
Float movement obstruction.
Pump will not shut off.
Liquid inflow matches or exceeds pump
output capacity.
Defective switch.
Check valve stuck or plugged.
Lift too high for pump.
Pump runs but does not
Inlet to impeller plugged.
discharge liquid.
Outlet flow is blocked.
Check valve stuck or plugged.
Lift too high for pump.
Pump does not deliver
rated capacity.
Low voltage, speed too slow.
Impeller or discharge pipe is clogged.
Pump cycles continually.
Check valve leaking.
For technical assistance, please contact:
800.701.7894 | littlegiant.com
Form 993554 Rev. 001 07/19
Probable Causes

Corrective Action

Connect pump to a dedicated GFCI circuit.
Turn on circuit breaker or replace fuse.
Remove the tank. Check float movement path. Remove any debris or
obstruction.
Replace pump.
Replace pump.
Connect pump to a dedicated GFCI circuit.
Larger pump required.
The high level switch should shut off the A/C unit or signal an alarm in
this condition if connected in the circuit correctly. Check to ensure that
the pump high level switch is connected to the A/C unit (or alarm cir-
cuit), and that the leads are connected to the correct switch terminals
for the application. Refer to
"High Water Level Switch Connection" on
page
4.
Check to ensure that the pump is level. If the pump is not level, it may
not activate, causing water to overflow from the tank. Place unit on a
flat and level surface.
Remove check valve and inspect for proper operation.
Check outlet tubing to ensure that it is not kinked or blocked. Clear
blocked tubing of slime and debris. Clean inlet and outlet piping.
Clear any blockage in the impeller housing.
Replace pump.
Replace pump.
Remove the tank. Check float movement path. Remove any debris or
obstruction.
Larger pump required.
The high level switch should shut off the A/C unit or signal an alarm in
this condition if connected in the circuit correctly. Check to ensure that
the pump high level switch is connected to the A/C unit (or alarm cir-
cuit), and that the leads are connected to the correct switch terminals
for the application. Refer to
"High Water Level Switch Connection" on
page
4.
Replace pump.
Remove check valve and inspect for proper operation.
Check rated pump performance.
Pull pump and clean.
Check outlet tubing to ensure that it is not kinked or blocked. Clear
blocked tubing of slime and debris. Clean inlet and outlet piping.
Remove check valve and inspect for proper operation.
Check rated pump performance.
Check that supply voltage matches nameplate rating.
Pull pump and clean. Check pipe for scale or corrosion.
Remove check valve and inspect for proper operation.
Franklin Electric Co., Inc. | Oklahoma City, OK 73157-2010
Copyright © 2019, Franklin Electric, Co., Inc. All rights reserved.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vcc-20uls

Table des Matières