Minimum Clearance To Combustible Enclosures - Napoleon Fireplaces GD33NR Mode D'emploi

Table des Matières

Publicité

5.3

MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES

GD33
COMBUSTIBLE
6" MINIMUM
29"
The GD33 requires a minimum enclosure
height of 35". For temperature requirements,
the enclosure space around and above the
appliance must be left unobstructed.
* See "VENTING" section.
NON-COMBUSTIBLE
BRICK
0" IF
NON-COMBUSTIBLE
2"
FINISHING IS USED
SUCH AS BRICK AND
STONE.
1"
1
20
/
"
4
MINIMUM
PLUS RISE *
2"
BGD33
COMBUSTIBLE
NON-COMBUSTIBLE
BRICK
4" MINIMUM
2"
29"
1"
MINIMUM
PLUS RISE *
2"
The BGD33 requires a minimum enclosure
height of 33". For temperature requirements,
the enclosure space around and above the
appliance must be left unobstructed.
35
0" IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
1
20
/
"
4
W415-0662 / D / 08.10.12