Page 1
USER MANUAL Ventilation unit with high efficiency air-to- air heat recovery Serie HRD EC 500 - 4000 Edition 04/21 Models HRD EC 500 HRD EC 1000 HRD EC 1500 HRD EC 2000 HRD EC 3000 HRD EC 4000...
Page 3
Attenzione!!! Togliere tensione prima di procedere Attention!!! Before proceeding remove power supply Attention!!! Coupez l'alimentation avant de procéder ¡Atención!!! Desconectar la fuente de alimentación antes de proceder HRD EC Descrizione Collegamenti Parametri Description Wiring Parameters Description Branchements Paramètres Descripción Cableado Parámetros By-pass BTE:...
Page 4
Non fornito Not provided Stato unità On/Off On/Off Unit state Etat de l'unité On/Off Estado de unidad de On/Off 230Vac Estate/Inverno Summer/Winter Stato modo Estate/Inverno Été/Hivèr Summer/Winter Unit state 10 11 12 Etat de l'unité Été/Hivèr Estado de unidad Verano/Invierno white Serrande esterne blue...
Page 5
Regolazione ventilatore con CO2 out …10V MAX 1,7VA (Password= 1) Fan control with CO2 out …10V MAX 1,7VA = 2 Régulation ventilateur avec CO2 Control de ventilador con CO2 Portata costante Constant air flow Flujo de aire constante out , …...
Page 6
PIR Sensor PIR sensore di presenza Open: OFF (Password= 1) Close: ON PIR occupant sensor = 4 PIR presence sensor Sensor de ocupante PIR Pressostati filtri Filter pressure switches PSTD Pressostats filtres Interruptores de presión de filtro shielded blue blue...
Page 7
MANUALE UTENTE Unità di ventilazione con recupero di calore aria- aria ad alta efficienza Serie HRD EC 500 - 4000 Edition 04/21 Models HRD EC 500 HRD EC 1000 HRD EC 1500 HRD EC 2000 HRD EC 3000 HRD EC 4000...
Electronic Control "HRD EC Manuale Utente Sommario Specifiche controllo: ................................4 Logica di controllo ................................4 Schermata principale Smart ..............................5 3.1. Uso dei tasti ................................5 3.2. Icone ...................................6 3.3. Menu terminale................................7 Display remoto ..................................8 4.1. Uso dei tasti ................................8 4.2. Icone ...................................9 4.3.
Page 9
Electronic Control "HRD EC Manuale Utente firmware 0.25 Rev.05 IT 3/ 23...
Electronic Control "HRD EC Manuale Utente 3 Schermata principale Smart Nella schermata principale il display target mostra il valore misurato dalla sonda di termoregolazione, oppure visualizza OFF. tramite i tasti F1 o F3 è possibile modificare la visualizzazione della schermata principale nei seguenti modi: :...
Electronic Control "HRD EC Manuale Utente 3.2. Icone Icona Descrizione Acceso Lampeggiante Standby L'unità è in STD-BY Allarme Almeno un allarme è attivo Tutti gli allarmi (attivi precedentemente) possono essere resettati Riscaldamento L'applicazione funziona in modalità Raffreddamento L'applicazione funziona in modalità ...
Electronic Control "HRD EC Manuale Utente 3.3. Menu terminale Service par 5.5 Password 1 Configurazione impianto par 5.8 Tipo impianto Conf. ventilazione Gestione defrost Sonda di regolazione Abilita ingresso AIR2 Cambio modo ...
Electronic Control "HRD EC Manuale Utente 4 Display remoto 4.1. Uso dei tasti Tasto premere e rilasciare premere a lungo Cambio velocità ventilatore Abilita profilo fasce orarie (psw) 1 Auto > 0 Abilita e disabilita modalità BOOST: Forza al massimo tutti i dispositivi disponibili per un tempo impostato.
Electronic Control "HRD EC Manuale Utente 4.2. Icone Icona Descrizione Acceso Lampeggiante Standby L'unità è spenta se OFF da remoto a display Off con programma settimanale attivo appare la scritta Allarme Almeno un allarme è attivo Tutti gli allarmi possono essere resettati Velocità...
Electronic Control "HRD EC Manuale Utente 4.3. Menu terminale remoto Fasce orarie par 5.2 Fasce orarie par 5.3 Notturno par 5.4 Service par 5.5 Password 1 Configurazione impianto par 5.8 Tipo impianto Conf. ventilazione ...
Electronic Control "HRD EC Manuale Utente 4.4. Cablaggio terminale remoto Max 100m Max 100m 4.5. Cablaggio ingressi digitali: ON-OFF remoto, cambio modo ESTATE-INVERNO, Allarme incendio. firmware 0.25 Rev.05 IT 11/ 23...
Electronic Control "HRD EC Manuale Utente 5 Lista Menu Menù per la configurazione delle fasce orarie, visualizzare stati ingressi uscite, impostazioni service, costruttore e assegnazione profili giornalieri. 5.1. Menu Configurazione Premere insieme Esc e “et Service (password) ...
Electronic Control "HRD EC Manuale Utente 5.4. Night () Night Notturno Abilita modo Night Off-On Ora partenza modo night 22:00 Ora fine modo night 07:00 Velocità ventilatore 26.0°C Set freddo Night ...
Electronic Control "HRD EC" Manuale Utente 6 Logica regolazione 6.1. Sonda di regolazione in temperatura La regolazione è basata sulla sonda di temperatura in mandata aria, tramite parametro è possibile spostare la regolazione sulla sonda di ripresa aria ambiente o sulla sonda del terminale. Di seguito i tre casi: 1) regolazione sulla sonda di mandata BTM ...
Electronic Control "HRD EC" Manuale Utente 6.3. Cambio Modo Caldo/Freddo Il cambio modo Caldo/Freddo può essere gestito da: Ingresso digitale o Aperto= Estate o Chiuso= Inverno Tastiera Remota BMS via Modbus Heating Automatico con sonda temperatura esterna: Se Te <...
Electronic Control "HRD EC" Manuale Utente (password) 1 (Tipo di gestione defrost) 0*= Off Disabilitato 1= Pre riscaldo attiva la resistenza di preriscaldo 2= Modulazione ventilatore riduce la velocità del ventilatore di mandata (password) 1 ...
Electronic Control "HRD EC" Manuale Utente 7 Allarmi 7.1. Allarme incendio La gestio e dell’allar e i ce dio da i gresso digitale può essere co figurato ei segue ti odi: (Tipo gestione allarme incendio) solo con = yes 0*= i caso di allar e i ce dio l’u ità...
Electronic Control "HRD EC" Manuale Utente 8 BMS Modbus RS485 Tipo di modbus Holding Register Comando di lettura: 03 (03Hex) Comando di scrittura: 16 (10Hex) : Indirizzo controllore protocollo Modbus default … 55 : Baudrate protocollo Modbus Esempio cablaggio rete 0= non usato 1= non usato 2= non usato...
Electronic Control "HRD EC" Manuale Utente 8.1. Variabili utente: Tipo di MODBUS: HOLDING REGISTER Comando di lettura: 03 (03Hex) Comando di scrittura: 16 (10Hex) Indirizzo Scrittura/Lettura Descrizione Valore Default Cambio modo: 16430 0 = Cool; 1 = Heat; 2 = Auto Stato On Off (Memorized into EEprom) 16431 0 = Off;...
Page 29
Electronic Control "HRD EC" Manuale Utente Indirizzo Lettura Descrizione ingressi uscite Valore Default 8432 Sonda temperature terminale remoto 18.3 °C -500 1100 Stato On-Off 8528 0 = Off; 1 = On 8960 Sonda di regolazione 17.5 °C -500 1100 8962 Velocità corrente ventilatore ripresa 1000 8963 Velocità...
Page 30
USER MANUAL Ventilation unit with high efficiency air-to- air heat recovery Serie HRD EC 500 - 4000 Edition 04/21 Models HRD EC 500 HRD EC 1000 HRD EC 1500 HRD EC 2000 HRD EC 3000 HRD EC 4000...
Page 31
Electronic Control "HRD EC" User Manual Index Control Features:.................................4 Control logic ..................................4 Smart Display ..................................5 3.1. Buttons function ................................5 3.2. Icon .....................................6 Remote display ...................................8 4.1. Buttons function ................................8 4.2. Icon .....................................9 4.3. Remote display ................................11 4.3.1. Digital input: remote ON-OFF, changeover Summer-Winter, Fire alarm..............11 Menu ...
Page 32
Electronic Control "HRD EC" User Manual firmware 0.25 Rev.05 EN 3/ 23...
Electronic Control "HRD EC" User Manual 3 Smart Display On the main screen the display shows the regulation temperature value or OFF By pressing F1 or F3 it is possible modify the main screen visualization as follows: : Time ...
Electronic Control "HRD EC" User Manual 3.2. Icon Icon Description Blink Standby Standby unit Alarm Active alarm Resettable alarm (not active) Active mode Winter Active mode Summer Freecooling Active Freecooling or Freeheating Freeheating firmware 0.25 Rev.05 EN 6/ 23...
Page 36
Electronic Control "HRD EC" User Manual Service Password 1 Plant configuration par 5.8 Plant type Air flow control Heat exchanger defrost anagement Regulation probe Enable AIR2 display Remote summer / winter changeover ...
Electronic Control "HRD EC" User Manual 4 Remote display 4.1. Buttons function Buttons Short press Long press Fan speed change Enable/disable clock program (psw) 1 Auto > 0 Start /Stop BOOST mode: The controller forces at maximum all the devices for a settable time.
Electronic Control "HRD EC" User Manual 4.2. Icon Icon Description Blink Standby Standby unit Off by clock program When display shows the unit in turned OFF by digital input Alarm Active alarm Resettable alarm (not active) Fan speed MIN Fan speed MED Fan speed MAX Fan speed AUTO...
Page 39
Electronic Control "HRD EC" User Manual Program setting par 5.2 Programs assignment par 5.3 Night par 5.4 Service par 5.5 par 5.8 Plant configuration Plant type Air flow control Heat exchanger defrost anagement ...
Electronic Control "HRD EC" User Manual 4.3. Remote display Max 100m Max 100m 4.3.1. Digital input: remote ON-OFF, changeover Summer-Winter, Fire alarm. firmware 0.25 Rev.05 EN 11/ 23...
Electronic Control "HRD EC" User Manual 5 Menu list On this menu it is possible to set the clock program range, visualize input and output status and access to service settings. 5.1. Menu root Press together Esc and “et ...
Electronic Control "HRD EC" User Manual 5.4. Night () Night Night mode enable Off-On Start time night mode 22:00 End time night mode 07:00 Fan speed Night Cooling set point 26.0°C ...
Electronic Control "HRD EC" User Manual 5.9. Parameter () (password) 1 (pass) 1 (antifreeze defrost) Antifreeze set point 5.0°C -5.0°C 15.0°C Defrost set point -4.0°C -15.0°C 10.0°C 5.10. Parameter () (password) 1 (pass) 1 ...
Page 45
Electronic Control "HRD EC" User Manual 5.12. Test mode () (pass) 1 Test Enable Test digital output (On-Off) Test damper by-pass Test electric heater Pre ...
Electronic Control "HRD EC" User Manual 6 Regulation logic 6.1. Temperature Control probe The control is based on the supply air temperature sensor, using the parameter it is possible to switch the control on the return air sensor or on the sensor placed on the terminal unit. The following three cases are then possible: 1) Control on the supply probe BTM ...
Electronic Control "HRD EC" User Manual 6.3. Cooling / heating mode changeover Cooling / heating mode can be switched by: Digital input o Open= Summer o Close= Winter Remote keyboard BMS via Modbus Heating Automatically with fresh air sensor: If Te <...
Electronic Control "HRD EC" User Manual ( Heat exchanger defrost management) 0*= Off Disable 1= Preheating Electric preheating is ON 2= Modulating fan It reduces the speed of the supply fan (password) 1 (set defrost) ...
Electronic Control "HRD EC" User Manual 7 Alarms 7.1. Fire alarm The management of a fire alarm from digital input may be configured as follows: ( Fire alarm management) only = yes 0*= Off, in case of fire alarm the unit is completely stopped 1= On, in case of fire alarm the dampers are open and the fans run at max speed 2= On, in case of fire alarm the dampers are open and only the return fans runs at max speed 7.2.
Electronic Control "HRD EC" User Manual 8 BMS Modbus RS485 Modbus Type Holding Register Read command: 03 (03Hex) Write command: 16 (10Hex) : Modbus protocol address default … 55 : Modbus protocol baud rate Example network cabling 0= not used 1= not used 2= not used 3= 9600 baud (default)
Page 51
Electronic Control "HRD EC" User Manual 8.1. User variables: MODBUS Point Type: HOLDING REGISTER Read command: 03 (03Hex) Write command: 16 (10Hex) Address write/read Description Value Default User Working Mode: 16430 0 = Cool; 1 = Heat; 2 = Auto On Off Status (Memorized into EEprom) 16431 0 = Off;...
Page 52
Electronic Control "HRD EC" User Manual Address read Description Input-Output Value Default 8432 Remote terminal temperature sensor 18.3 °C -500 1100 State On-Off 8528 0 = Off; 1 = On 8960 Regulation Probe 17.5 °C -500 1100 8962 Current Return Fan Speed 1000 8963 Current Supply Fan Speed 1000...
Electronic Control "HRD EC" Mode d'emploi 3 Afficheur Smart Sur l’écra pri cipale, le viseur o tre la valeur esurée par la so de de térmoregolation, ou il montre OFF. par les clés F1 ou F3, vous pouvez modifier la visualisation de la manière suivante : :...
Electronic Control "HRD EC" Mode d'emploi 3.2. Icone Icône Description illuminé Clignotant Standby L'unità è in STD-BY Alarme Au moins une alarme est active Toutes les alarmes peuvent être réinitialisées Etat Chaud L'application fonctionne en mode Etat Froid L'application fonctionne en mode ...
Page 59
Electronic Control "HRD EC" Mode d'emploi Service par 5.5 Password 1 Configuration installation par 5.8 Type installation Configuration ventilation en automatique Type de gestion dégivrage Sonde de régulation Activer entrée AIR2 sur le clavier ...
Electronic Control "HRD EC" Mode d'emploi 4 Clavier 4.1. Utilisation de clés Clé pression brève pression longue Changement vitesse ventilateur Active profile tranches horaires (psw) 1 Auto > 0 Active et désactive mode BOOST: Force au maximum tous appareils disponibles pour un temps indiqué...
Electronic Control "HRD EC" Mode d'emploi 4.2. Icone Icône Description illuminé Clignotant L'unité est arrêté si OFF rémotisé sur l’écra Standby Off avec programme hebdomadaire activ o voit l’i dicatio Alarme Au moins une alarme est active Toutes les alarmes peuvent être réinitialisées Fan de vitesse MIN...
Page 62
Electronic Control "HRD EC" Mode d'emploi Configuration profils par 5.2 Attribution profils par 5.3 Nocturne par 5.4 Service par 5.5 Password 1 Configuration installation par 5.8 Type installation Configuration ventilation en automatique Type de gestion dégivrage ...
Electronic Control "HRD EC" Mode d'emploi 5 Liste Menus Menu pour la configuration des créneaux horaires, visualiser les états des entrées et des sorties, paramètres service et constructeur et attribution profils quotidiens. 5.1. Menu Configuration Appuyer sur Es et “et ...
Electronic Control "HRD EC" Mode d'emploi 5.4. Night () Night Nocturne Active le mode Night Off-On Heure départ mode night 22:00 Heure fin mode night 07:00 Vitesse ventilateur Consigne froid Night 26.0°C ...
Electronic Control "HRD EC" Mode d'emploi 6 Logique régulation 6.1. Sonde de régulation en température Le réglage est basé sur le sonde de température de l'air de soufflage, il est possible déplacer la sonde de régulation sur l'air de reprise ou sur la sonde du terminal sur le terminal. Les trois cas suivantes: régulation sur la sonde d'alimentation ...
Electronic Control "HRD EC" Mode d'emploi 6.3. Changement Mode Chaud/Froid Le changement de mode Chaud/Froid peut être géré à partir de: Entrée numérique o Ouvert= Froid o Fermé= Chaud Clavier à distance BMS via Modbus Chauffage Automatique avec sonde de température externe: Si Te <...
Electronic Control "HRD EC" Mode d'emploi Suit le parcours du paramètre pour permettre le dégivrage: (mot de passe) 1 ( Type de gestion dégivrage 0*= Off 1= Préchauffage Active la batterie de pré-chauffage 2= Modulation ventilateur Réduit la vitesse du ventilateur de soufflage ...
Electronic Control "HRD EC" Mode d'emploi 7 Alarmes 7.1. Alarme incendie La gestion de l'alarme incendie à partir de l'entrée numérique peut être configurée des façons suivantes : (Type gestion alarme incendie) seulement avec = yes 0*= Off, en cas d'alarme incendie l'unité s'éteint 1= On, en cas d'alarme incendie, les trappes s'ouvrent et les ventilateurs se mettent à...
Electronic Control "HRD EC" Mode d'emploi 8.1. Variables utilisateur : Type de MODBUS : HOLDING REGISTER Commande de lecture : 03 (03Hex) Commande d'écriture : 16 (10Hex) Indirizzo Scrittura/Lettura Descrizione Valore Default Changement mode: 16430 0 = Cool; 1 = Heat; 2 = Auto Etat On Off (Memorized into EEprom) 16431 0 = Off;...
Page 75
Electronic Control "HRD EC" Mode d'emploi Indirizzo Lettura Descrizione ingressi uscite Valore Default 8432 Sonde température terminal rémotisé 18.3 °C -500 1100 Etat On Off 8528 0 = Off; 1 = On 8960 Sonde de régulation 17.5 °C -500 1100 8962 Vitesse courant ventilateur échappement 1000 8963 Vitesse courant ventilateur alimentation...
Page 76
MANUAL DE USUARIO Unidad de ventilación con recuperación de calor aire- aire de alta eficiencia Serie HRD EC 500 - 4000 Edition 04/21 Models HRD EC 500 HRD EC 1000 HRD EC 1500 HRD EC 2000 HRD EC 3000 HRD EC 4000...
Page 77
Control electrónico "HRD EC" Manual de usuario Índice Funciones de Control:................................4 Lógica de control ................................... 4 Pantalla inteligente ................................5 3.1. Función de los botones ..............................5 3.2. Icono ..................................... 6 Visualización remota ................................8 4.1. Función de los botones ..............................8 4.2.
Page 78
Control electrónico "HRD EC" Manual de usuario firmware 0.25 Rev.05 ES 3/ 23...
Control electrónico "HRD EC" Manual de usuario 1 Funciones de Control: Selección automática / manual de la velocidad del ventilador Gestión de válvulas flotantes de conmutación Gestión de válvulas flotantes de calefacción Gestión de bobina de agua anticongelante ...
Control electrónico "HRD EC" Manual de usuario 3 Pantalla inteligente En el monitor principal la pantalla muestra el valor de temperatura de regulación o DESACTIVADO (OFF) Pulsando F1 o F3 es posible modificar la visualización de la pantalla principal de la siguiente manera: Hora Modo Sonda de regulación...
Control electrónico "HRD EC" Manual de usuario 3.2. Icono Icono Descripción Encendido Parpadear Espera Unidad de espera Alarma Alarma activa Alarma reiniciable (no activa) Modo activo Invierno Modo activo Verano Refrigeración Refrigeración libre Calefacción libre libre Calefacción activas libre firmware 0.25 Rev.05...
Page 82
Control electrónico "HRD EC" Manual de usuario Servicio par 5.5 contraseña 1 Configuración de la planta par 5.8 Tipo de planta Control de flujo de aire Gestión de desempañador Sonda de regulación Habilitar pantalla AIR2 ...
Control electrónico "HRD EC" Manual de usuario 4 Visualización remota 4.1. Función de los botones Botones Pulsar brevemente Pulsar de modo prolongado Activar/desactivar programa del Cambio de velocidad del ventilador reloj (psw) 1 Mín Máx. Auto ...
Control electrónico "HRD EC" Manual de usuario Botones Pulsar brevemente Pulsar de modo prolongado Pulse en el botón para guardar Acceso al menú de programación 4.2. Icono Icono Descripción Encendido Parpadear Espera Unidad de espera Apagado por programa del reloj Cuando la pantalla muestra...
Page 85
Control electrónico "HRD EC" Manual de usuario reloj Configuración de rango de programa de tiempo de par 5.2 Asignación de programa de día par 5.3 Noche par 5.4 Servicio par 5.5 contraseña 1 Configuración de la planta par 5.8 ...
Control electrónico "HRD EC" Manual de usuario 5 Lista En este menú se puede ajustar el rango de programas de reloj, visualizar estados de entrada y salida y acceder a la configuración del servicio. 5.1. Raíz de menú Presione "Esc" y "Set" al mismo tiempo ...
Control electrónico "HRD EC" Manual de usuario 5.4. Noche() Noche Activar el modo nocturno Off-On Hora de inicio del modo nocturno 22:00 Hora de finalización del modo nocturno 7:00 Velocidad del ventilador ...
Control electrónico "HRD EC" Manual de usuario 5.12. Modo de prueba () (aprobar) 1 Mín. Máx. Habilitación de prueba Prueba de salida digital (Encendido/Apagado) Prueba de derivación de regulador ...
Control electrónico "HRD EC" Manual de usuario 6 Lógica de regulación 6.1. Sonda de control de temperatura El control se basa en el sensor de temperatura del aire de alimentación, utilizando el parámetro es posible conmutar el control del sensor de aire de retorno o del sensor colocado en la unidad terminal. Los tres casos siguientes son posibles: 1) Control de la sonda de alimentación BTM ...
Control electrónico "HRD EC" Manual de usuario 6.3. Conmutación del modo de calefacción / refrigeración Modo de calefacción / refrigeración puede conmutarse mediante: Entrada digital o Abierto= Verano o Cerrado= Invierno Teclado remoto BMS a través de Modbus ...
Control electrónico "HRD EC" Manual de usuario Aquí se encuentra la ruta de acceso del parámetro para activar la función de descongelación: (contraseña) 1 ( descongelador de intercambiador de calor) Gestión de 0*= Off Desactivar 1= precalentamiento Precalentamiento eléctrico está...
Control electrónico "HRD EC" Manual de usuario 7 Alarmas 7.1. Alarma de incendio La gestión de una alarma de incendio desde la entrada digital puede ser configurada de la siguiente manera: Gestión de alarmas de incendios sólo = sí...
Control electrónico "HRD EC" Manual de usuario 8 Modbus RS485 BMS Registro de la soporte tipo Modbus Comando de lectura: 03 (03Hex) Escriba el comando: 16 (10Hex) : Dirección de protocolo Modbus predeterminado (1...255) : Velocidad en baudios del protocolo Modbus Example network cabling 0= no se usa 1= no se usa...
Control electrónico "HRD EC" Manual de usuario 8.1. Variables de usuario: Tipo de punto MODBUS: REGISTRO DE SOPORTE Comando de lectura: 03 (03Hex) Escriba el comando: 16 (10Hex) Dirección de Mín. Máx. lectura/escritura Descripción Valor Predeterminado Modo de trabajo: usuario 16430 0 = frío;...
Page 98
Control electrónico "HRD EC" Manual de usuario Dirección de Mín. Máx. lectura Descripción de entrada/salida Valor Predeterminado Sensor de temperatura del 8432 18,3 °C -500 1100 terminal remoto Estado On-Off 8528 0 = desactivado; 1 = activado 8960 Sonda de regulación 17,5 °C -500...
Page 99
Eurofred S.A. Marqués de Sentmenat 97 08029 Barcelona www.eurofred.es...