Mounting
1
2
2.2.1
screw in
>> conduit coupling
conduit coupling
3
wire
clamping
Receiver / Power supply
GNYE wire
(green/yellow)
1.1
1.2
screw in
>> DEHNpipe, DPI ME 24 N A2G
GNYE
2.2
fix
>> DEHNpipe
DPI ME 24N A2G
BK wire (black)
RD wire (red)
UL requirements
1. This device are intended for ordinary indoor us on communication loop
circuits that are isolated from the Public Switched Telephone Network.
2. The protector shall be secured using the methods described in this
instruction.
3. Proper grounding continuity shall be determined.
+
4. Please install the protector in accordance with the applicable
-
requirements of the National Electrical Code, Article 800 or other
GNYE
applicable local codes.
5. The maximum circuit current for UL 497 B applications is limited to
100 mA.
Tabulation Strike voltage in accordance with UL 497 B (Protectors for Data Communication and Fire Alarm Circuits)
Type
2.1
connection
DPI ME 24 N A2G
(+) BU
wire (blue)
+
(-) BK
wire (black)
-
GNYE
wire(green/yellow)
+
-
GNYE
1464 / 08.18 / 63675
Strike voltage 100 Volts / sec
Surge voltage 100 Volts / μ sec
Line to Ground
Line to Line
Line to Ground
Part No.
min.
max.
min.
max.
min.
max.
37 V
49 V
74 V
98 V
37 V
52 V
929 921
© COPYRIGHT 2018 DEHN + SÖHNE / protected by ISO 16016
Line to Line
min.
max.
74 V
104 V