3.
Installation instructions
3.1
General
The. appliance. must. be. installed. on. floors. with.
corresponding. bearing. capacity;. if. the. existing.
arrangement. does. not. conform. to. this. necessary.
requirement,. appropriate. measures. must. be. taken. (e.g..
using.a.bearing.plate.for.load.distribution).
Adequate.access.for.cleaning.the.appliance,.the.flue.
gas.duct.and.the.chimney.must.be.ensured.
3.2
Chimney connection
A.suitable.chimney.(minimum.cross.section,.chimney.
draught,. tightness,. etc.). is. crucial. for. good. stove.
functioning.. Consult. the. chimneyer. prior. to. installing.
the. stove.. Chimney. specifications. can. be. found. in. the.
attached.technical.data.table..The.best.efficiency.will.be.
achieved.by.combustion.with.the.door.closed.and.with.
the.chimney.draught.about.10.Pa.(Pascal)..If.the.chimney.
draught.is.bigger.than.15.Pa,.we.recommend.to.reduce.
it. by. half. closing. the. secondary. air. inlet.. If. this. air. is.
not.regulated,.an.additional.flue.flap.should.be.mounted..
10. Pa. chimney. draught. with. min.. 177. cm
chimney.flue.cross.section.at.usual.atmospheric.pressure.
can.be.achieved.if.the.effective.height.of.the.chimney.is.
c..5.m.(measured.from.the.shrunk. ring.to.the.orifice)..
The.chimney.entrance.must.be.provided.with.a.shrunk.
ring. and. a. rosette.. The. blind. cover. can. be. replaced.
with.the.smoke.flue.duct.orifice.depending.on.the.flue.
duct.being.connected.to.the.back.or.the.upper.flue.gas.
outlet.. Tightness. and. firmness. of. connections. is. very.
important..
The. Type. 1. stove. (see. the. technical. data. table). is.
equipped. with. a. self-closing. door.. This. stove. can. be.
mounted.to.the.chimney.flue.together.with.another.solid.
fuel.stove.under.the.following.conditions:
a).. if.several.appliances.are.connected.to.one.chimney.
flue,.only.appliances.from.one.floor.and.from.one.
user.can.be.connected..
Two. users. from. the. same. floor. can. use. one.
common. chimney. flue. only. if. approved. by. a.
relevant.building.office.
b). in. existing. objects,. two. local. closable. solid. fuel.
appliances. can. be. connected. to. one. common.
chimney.flue.from.two.floors.of.one.unit.(e.g..a.
family.house),.if.approved.by.the.chimneyer..The.
Type. 2. stove. (see. the. technical. data. table). does.
not. have. a. self-closing. door.. Fire. with. the. door.
open.is.possible.only.if.there.is.someone.near.the.
03/2011
stove..When.leaving.the.stove,.close.the.door.of.
the.furnace..
3.3
Installing a fireplace insert
For. building. in. a. fireplace. insert. expert. knowledge. is.
necessary..However,.if.you.decide.to.install.a.fireplace.by.
yourself,.please.follow.the.instructions.below:
l.. .The.diameter.of.the.chimney.for.connecting.must.
be.at.least.18.cm.and.the.chimney.must.have.an.
effective.height.of.at.least.5.m.
2.. Eventual.air.condition.piping.must.be.at.least.40.cm.
away. from. flammable. building. structures. or. it.
must. be. proved. that. the. heat. transfer. from. the.
piping.cannot.cause.ignition.of.the.structures..The.
convection. airtemperature. near. the. insert. can. be.
as.high.as.300.°C.!
3.. Build. the. fireplace. so. that. its. walls. are. at. least. 5. cm.
from. the. rear. and. side. walls. of. the. fireplace.
insert. sheathing.. The. spaces. serve. for. cooling.
air. circulation,. which. prevents. the. surrounding.
structures. from. overheating.. Do. not. cover. these.
spaces.from.above.nor.from.below.
4.. In.the.lower.part.of.the.fireplace.(under.the.insert).
(Φ15cm).
vent. holes. min.. 150. cm
2
input.must.be.made.
5.. Make. vent. holes. for. heated. convection. air.
output. in. the. uppermost. part. of. the. fireplace.
superstructure.
Total. cross. section. of. the. vent. holes. must. be. at.
least.150.cm
6.. The.floor.in.front.of.the.fireplace.must.be.made.
from.inflammable.material.(tile,.stone,.brick,.etc.).
up.to.at.least.80.cm.in.front.of.the.fireplace.and.
40.cm.at.the.sides.over.the.contour.of.the.fireplace.
insert.. The. floor. for. the. appliance. must. have.
corresponding.load.capacity.
7.. Sufficient. access. for. appliance,. smoke. flue. duct.
and. chimney. cleaning. must. be. ensured.. The.
inserts.have.upper.flue.gas.outlet.only.
8.. Eventual. modifications. of. the. insert. must. be.
consulted.with.the.manufacturer.
The.insert.must.be.installed.so.that.it.can.always.be.
removed.from.the.surrounding.structure.if.necessary.
During. appliance. installation,. all. local. regulations,.
including. regulations. related. to. national. and. European.
standards,.must.be.complied.with..A.professional.project.
should.be.elaborated.prior.to.installation..
Before. the. first. fire. is. made,. everything. must. be.
checked. by. a. chimneyer,. who. will. issue. a. written.
revision.report..Save.the.report.for.future.reference!
. for. cold. convection. air.
2
..
2