General installation requirements for all heater cables
1.
The installation should be carried out to VDE standard 0100 by a professional electrician.
2.
The water pipes must be earthed. A residual current device (30 mA RCD) must be in circuit.
3.
Install the PATURA frost protection heater cable only in accessible places.
Do not lay behind walls.
4.
Ensure that the heater cable is laid taut along the underside of the pipe. Attach every 30 cm with insulating
tape. Knicking of the cable must be prevented (min. 50 mm dending radius).
5.
If the pipe comes out of the ground, the heating cable must be installed up to the frost line.
6.
The heater cable should never be laid so as to touch other heater cables.
7.
The heating cable must never be installed overlapping. Wind left over length at the end of the cables in coils
around the cable (minimum clearance between loops 15 mm).
8.
The water pipe, with its heater cable, should be covered with pipe insulation. (min. 10 mm)
9.
The heater cable should be protected against damage generally – but particularly against animal biting/
chewing damage.
10.
Kinks in the heating cable should be avoided. (min. bend radius 50 mm)
11.
The PATURA anti-freeze heating cable must not be immersed in liquids.
12.
Connect the PATURA heating cable to a 230 volt socket.
13.
In the case of plastic water pipes, first wrap these with aluminium tape before affixing the heater cable, so as
to improve the thermal conductivity.
The PATURA frost protection heater cable is a quality product and guarantees a high degree of efficiency.
We do not accept any liability for not professionally executed installation.
The warranty becomes void if the heating cable is modified (e.g. cutting off the plug or thermostat,
shorten cable).
Frost protection with the use of heater cable (16 Watt/m):
Water pipe diameter
Without pipe insulation
With 13 mm pipe insulation -45°C
15 mm
22 mm
28 mm
-20°C
-13°C
-10°C
-45°C
-40°C
35 mm
42 mm
48 mm
-7°C
-5°C
-4°C
-40°C
-35°C
-30°C
60 mm
76 mm
-3°C
-2°C
-25°C
-20°C