INDICATION
1. NORMAL (GREEN LED)
2. BACKUP (YELLOW LED)
3. FAULT (RED LED)
4. OUTPUT SOCKET (Surge
protection only)
5. OUTPUT SOCKET (Surge
protection + UPS)
6. POWER SWITCH
7. RESET CIRCUIT BREAKER Reset circuit breaker protection
8. INPUT POWER CORD
9. OUTPUT PHONE JACK
10. INPUT PHONE JACK
Voltage DJ
The Voltage DJ guard the incoming voltage. When the voltage exceeds a limit, the
UPS will be activated. With the dipswitches 1 and 2 the lower limit can be set and the
higher limit can be set with dipswitch 3.
Lowest limit
160V (default)
1: OFF
1: ON
2: OFF
2: OFF
ENGLISH
STATUS
Lights up when supply is in normal condition and
flashes when UPS is regulating
Lights up when battery is in backup mode and
flashes when battery has a low voltage
Flashes when malfunction or overload occurs
Connect with load equipment. Surge protection
only.
Connect with load equipment. Surge protection +
UPS
Press the "Power" button for 4 seconds to turn
on/off the UPS.
Connect to AC Power
Connect to the Tel/Fax/Modem by another phone
line.
Insert the phone line into the jack.
180V
196V
1: OFF
2: ON
2
Highest limit
265V (default)
275V
3: OFF
3: ON