Visual indicators
Parallel operation
INSTALLATION
Green LED = normal operation, Vdc>42V
Fast blinking green LED = communication failure
Slow blinking green LED = rectifier in standby mode,
presence of AC and Vdc=0V
Green LED + red LED = Minor alarms except power
derating and current limitation
Green LED + blinking red LED = Power derating, Current
limitation
Green LED off + red LED = major alarm, no power on
output
Slope on output + Active load sharing by system controller
The SMi2000HD module must be installed by qualified
people.
A module is provided for fixing on a 19 inches standard
rack.