7XV5654-0BA00
Fibre Optic (FO) connections
Only optical fibres prepared according the regulations are to be used. The admissible
optical budget inclusive all splices is to be observed.
FO-types (only multimode) and maximum distance see technical data.
Transmitter diodes are printed with Tx (Note: No Tx – fiber in this device)
Receiver diodes are printed with Rx.
The FO-cables must be crossed, that means a FO-connection is done between Tx
output and Rx input and vice versa.
Connections at X1
After the connection of a plug to the 9 pole Sub-D socket at the device (X1) it should be
screwed. For temporally use it's not necessary to screw it.
Commissioning
Clip the Sync.-Transceiver on the top–DIN rail according EN 50022 with the help of clip-
on mounting. Do not make any changes at the device.
Check whether the operation data comply with the values on the rating plate. Not
change any DIP-switch at the device, before reading this manual.
Connect FO cable to FO receiver (Rx) with the help of ST plugs. Be carefully when
connecting the FO plugs and avoid any dust at the FO – connections.
Connect to Sub-D socket X1 and screw them for permanent use.
Connect the alarm relay terminals X7.
Connect auxiliary power to the terminals X2 (DC: L+ / AC: L1 and DC: L- / AC: N).
The device is ready for use after switching on the auxiliary power supply. The green
LED `RUN´ lights up.
Maintenance
The signal converter requires no maintenance. For cleaning please use a dry and free
of fuzz rag. Put the caps onto the FO-interfaces to avoid dust pollution and interference
from sun light or any artificial light source.
Do not use any liquid agents or substances for cleaning.
C53000-B1175-C168-1
Note
When installing optical fibres the prescripted bending radius is to
be observed.