EN
A
MOUNTING
Mounting in electrical cabinet, false ceiling or floor
or wall mounting. Make sure the unit is mounted
on a solid surface to securely fix the unit.
The unit shall be mounted in such a way, that the
back side becomes inaccessible.
[1] Choose the optimal location: flat and large
surface
[2] Select the relevant screws according to the
material of the mounting site and mount the
animeo Power Supply DC.
Mains connection shall not be accessible after
correct installation.
CHARACTERISTICS
Supply voltage
Stand-by current (IEC 62301)
Stand-by power (IEC 62301)
DC output@24 V DC (100 %)
DC output@24 V DC (ED 50 %)
Terminals
Operating temperature
Relative humidiy
Material of housing
Housing dimensions (w x h x d)
Weight
Degree of protection
Protection class
Conformity
CABLE
Connection
220 - 240 V AC
24 V DC
220 - 240 V AC / 50/60 Hz
45 mA@230 V/50 Hz
1.8 W@230 V/50 Hz
2.5 A
4.5 A
Spring connectors
0 °C to + 45 °C
Max. 85 %
PC-ABS
130 x 180 x 62 mm
460 g
IP 20
II
www.somfy.com/ce
Cables
Min.: 2 x 1.5 mm
/15 AWG
2
Max.: 2 x 2.5 mm
/13 AWG
2
Min.: 2 x 1.5 mm
/15 AWG
2
Max.: 2 x 2.5 mm
/13 AWG
2
B
WIRING
[1] Use cable tie and cable grommet!
[2] Tool for all terminals
[3] Wiring diagram
C
MAXIMUM OUTPUT CURRENT
[1] 2.5 A (100 % permanent),
4.5 A (intermittent operation
t
3 min./t
on
Temperature-resistance
+ 90 °C
3 min.)
off
Max. distance
10 m/33 ft
animeo POWER SUPPLY DC . REF. 5010767D -