Carel MChiller Mode D'emploi page 108

Régulation pour chiller / pompe à chaleur
Masquer les pouces Voir aussi pour MChiller:
Table des Matières

Publicité

FRE
Index Size Ref. Type Min/Max
210
1
S002 INT
0..2
212
1
S022 INT
0..59
214
1
S008 INT
0..999
215
1
S010 INT
0..2
216
1
S011 INT
0..101
217
1
S012 INT
0..999
218
1
S014 INT
0..2
219
1
S015 INT
0..101
-
220
2
S016 REAL
999.9..999.9
222
2
S017 REAL 0..100
224
2
S018 REAL 0..100
226
1
S019 INT
0..300
227
2
REAL
229
2
Sprb REAL
231
2
S025 REAL 0..999.9
233
1
S026 INT
0..999
234
1
S027 INT
0..999
-
235
2
S028 REAL
999.9..999.9
237
2
S029 REAL 0..99.9
241
2
S031 REAL 0..999.9
243
1
S032 INT
0..999
246
2
S034 REAL 0..99.9
248
2
S035 REAL 0..99.9
250
2
S036 REAL 0..100
252
2
S037 REAL 0..100
254
2
S039 REAL -99.9..99.9
256
2
S040 REAL S039..99.9
258
1
S041 INT
0..999
-
259
2
S042 REAL
999.9..999.9
261
1
S044 INT
0..999
262
1
S045 INT
0..999
263
1
S046 INT
0..99
264
1
S047 INT
0..99
265
1
S048 INT
0..999
266
1
S049 INT
0..999
267
1
S050 INT
0..999
272
1
S053 INT
0..2
274
2
S054 REAL 0..999.9
278
1
S056 INT
20..999
-
279
2
S057 REAL
999.9..999.9
281
2
S058 REAL 0..999
283
1
S059 INT
0..999
284
2
S060 REAL -99.9..99.9
286
1
Hc00 INT
0..3/4
287
1
Hc01 INT
0..1
288
1
Hc03 INT
0..2
289
1
Hc04 INT
0..1
290
1
Hc05 INT
0..1
291
1
Hc06 INT
0..6
292
1
Hc07 INT
0..6
293
1
Hc08 INT
0..6
108  |  7. Tableaux supervision
R/W UoM
Description
R/W
S002 - Source pump 1 manual mode (0=AUTO, 1=OFF, 2=ON)
R/W min
Time band minute
R/W h
S008 - Source fan 1 circ.1 maintenance hour threshold (x100)
R/W
S010 - Source fan ON/OFFcirc.1 manual mode (0=AUTO, 1=OFF, 2=ON)
R/W %
S011 - Source fan inverter circ.1 manual mode(0=AUTO, 1=0%, 2=1%, .. 101=100%)
R/W h
S012 - Source fan 1 circ.2 maintenance hour threshold (x100)
R/W
S014 - Source fan ON/OFF circ.2 manual mode (0=AUTO, 1=OFF, 2=ON)
R/W %
S015 - Source fan inverter circ.2 manual mode (0=AUTO, 1=0%, 2=1%, .. 101=100%)
R/W °C/°F
S016 - Source fan temp. threshold for cold climates
R/W %
S017 - Source fan min speed for cold climates
R/W %
S018 - Source fan speed up speed for cold climates
R/W s
S019 - Source fan speed up time for cold climates
R/W %
FC_PrwReq - Free-Cooling regulation ramp
R
°C/°F
SPrb - Source external air temperature
R/W °C/°F
S025 - Low noise source fan setpoint in cooling
R/W s
S026 - Compr. delay ON since the source pump ON
R/W s
S027 - Source pump delay OFF since the compr. OFF
R/W °C/°F
S028 - Source fan cool setpoint
R/W °C/°F
S029 - Source fan heat setpoint
R/W °C/°F
S031 - Source fan cool setpoint at startup
R/W s
S032 - Source fan cool startup delay
R/W K/R
S034 - Source fan cool differential
R/W K/R
S035 - Source fan heat differential
R/W %
S036 - Source fan inverter min speed
R/W %
S037 - Source fan inverter max speed
R/W °C/°F
S039 - Defrost start threshold
R/W °C/°F
S040 - Defrost start threshold reset
R/W min
S041 - Defrost start delay
R/W °C/°F
S042 - Defrost end threshold
R/W s
S044 - Defrost begin delay before actuating the 4 way valve
R/W s
S045 - Defrost ending delay after actuating the 4 way valve
R/W min
S046 - Defrost min duration
R/W min
S047 - Defrost max duration
R/W s
S048 - Dripping duration
R/W s
S049 - Post dripping duration
R/W min
S050 - Delay between defrosts
R/W
S053 - Defrost synchronization type (0=Independent, 1=Separated, 2=Simultaneous)
R/W bar/psi S054 - Delta press. to reverse the 4 way valve
R/W s
S056 - Duration of smart start function
R/W °C/°F
S057 - Antifreeze source alarm threshold
R/W K/R
S058 - Antifreeze source alarm differential
R/W s
S059 - Antifreeze source alarm delay time at 1K below threshold
R/W K/R
S060 - Source external air temperature offset
Hc00 - Analog input 3 config. (0=Not used, 1=Source temp., 2=Discharge temp., 3=Suction temp.,
R/W
4=Source water delivery temp.)
R/W
Hc01 - Analog input 4 and 5 config. (0=Pressure, 1=Temp.)
R/W
Hc03 - Analog input 6 config. (0=Not used, 1=Remote setpoint, 2=Source temp.)
R/W
Hc04 - Analog input 7 config.(0=Not used, 1=Suction temp.)
R/W
Hc05 - Analog input 6 config. of Slave board (0=Not used, 1=Remote setpoint)
Hc06 - Digital input 4 config. (0=Not used, 1=Compr.2 circ.1 overload, 2=Remote ON/OFF, 3=Cool/Heat,
R/W
4=2nd SetPoint, 5=Remote alarm , 6=User pump 1 overload)
Hc07 - Digital input 5 config. (0=Not used, 1=Compr.2 circ.1 overload, 2=Remote ON/OFF, 3=Cool/Heat,
R/W
4=2nd SetPoint, 5=Remote alarm , 6=User pump 1 overload)
R/W
Hc08 - Digital input 6 config. (0=Not used, 1=Compr.2 circ.1 overload, 2=Remote ON/OFF, 3=Cool/Heat,
µChiller +0300053FR rel. 1.3 – 30.10.2019