Assembly Instruction (original)
gesis
NRG GST18i5
®
Connecting module
• All gesisNRG system components may only be installed, commissioned and maintained by
qualified electricians.
• Personnel who install, program, operate or maintain this device must have read and
understood these instructions.
• The relevant standards, guidelines, regulations and provisions of the respective country
must be observed.
• Protective measures and mechanisms must correspond to applicable regulations.
• Damaged products may neither be installed nor operated.
• In case of a defect, please return the component to Wieland Electric.
• Never use components from third-party manufacturers. No guarantee shall be offered for
damage resulting from a combination with third-party components.
• Please keep these instructions in a safe place for later reference.
• Use only blue system components for blue flat cables (DIMM).
• Use only black system components for green and black flat cables (BASIC).
• No hazardous interchangeability with systems based on IEC 60309, IEC 60320, IEC 60906
and with national connector and socket systems for home use.
• Interchangeability between installation connector systems from different manufacturers is
not automatically prevented by compliance with EN 61535.
• Compatibility with products from other manufacturers cannot be guaranteed.
• Installation connectors do not replace national connector/socket systems for home use.
• Unused connectors must be provided with closures in easily accessible areas.
• If the feed-in module is later shifted on the flat cable, then the contact openings in the
cable must be closed by cable patches!
• Never install or remove while energized.
®
The components of the GST18
system are used to distribute energy and/or data in building
interiors.
1
Scope of supply (pre-assembled)
The supplied components and cables may neither be changed nor modified.
• Baseplate 1x
• Equipped connecting module 1x
• Cover 1x
2
Borehole dimensioning
3
Mounting
1.
Lay the flat cable in a suitable
cable routing system. Note the
laying direction for the outlet di-
rection of the connectors. Insert
the flat cable concisely into the
coded baseplate
(92.050.1553.1 for green/black
cable, 92.051.5553.0 for blue ca-
ble).
2.
Use the two mounting holes to
attach the optional baseplate to
the desired subsurface.
Doc. # BA001021 - 05/2015 (Rev. A)
®
gesis
NRG BASIC 92.051.5453.1
®
gesis
NRG DIMM 92.051.5553.0
IN FO
C A U TIO N !
W A RN IN G
Wieland Electric GmbH
Brennerstrasse 10-14
Bamberg 96052 Germany
Tel.:
+49 951 9324-0
Fax:
+49 951 9324-198
Internet: www.wieland-electric.com
Email: info@wieland-electric.com
3.
Close the connecting module and
latch it with a clearly audible
click.
4.
Tighten all of the contact screws
consecutively (0.5 Nm).
5.
Close the cover and latch it with a
clearly audible click.
Caution:
The screws are not all correctly
tightened if the cover does not
completely close!
6.
Attach GST18i5 connector and latch it with a clearly audible click.
4
Removal
1.
Use a tool (screwdriver) to release
the connector interlock and re-
move the connector.
2.
Use a screwdriver to press the interlock lugs
in the direction of the arrow and open the
cover.
3.
Loosen the contact screws.
4.
Use a tool (screwdriver) to
unlatch the baseplate interlock
and to release the module from
the flat cable. Use cable patch to
seal openings in the insulation.
5
Technical data
Rated voltage
Rated current
Protection class
Protection type
Tightening moment of the
contact screws
gesisNRG
GST18i5
250 / 400 V
20 A
I
IP20 (inserted IP40)
0.5 Nm
EN