GCSA24, GCCA24, GCSB24, GCCB24, GCSG24, GCCG24, GCSR24, GCCR24 PRODUCT INFORMATION
LIGHT OUTPUT IN PERCENTAGE WHEN MEASURED
FROM THE FOLLOWING DIRECTIONS - PER UL 1638
Wall and Ceiling Mount Horizontal Dispersion
Ceiling Mount Vertical Dispersion
30
60
90
Degrees
0
30
60
90
AMBER, BLUE & GREEN Lens Strobe Current Ratings
Use with GCSA24, GCCA24, GCSB24,
GCCB24, GCSG24, GCCG24 Products
Regulated 24VDC Max.
Candela
Operating Current (mA)
15
30
75
95
115
NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS:
16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE
RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM
OPERATION.
Minimum SPL
Horn Mode
ANSI/UL 464
Temp 3 2400Hz
Temp 3 Mechanical
Continuous 2400Hz
Continuous Mechanical
NOTICE:
w THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE ONLY.
w THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUTPUT RATING. WHILE
THE HORN IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE CONTINUOUS MODE. UNITS HAVE BEEN TESTED TO 0°C, 49°C AND
93% HUMIDITY.
* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 sound level Required for public mode fire protection service. These settings are
acceptable only for private mode fire alarm signaling use. Use the high dBA setting for public mode applications.
IV. WIRING
Wiring for synchronized strobes and horns.
Using this method you may:
Use only two wires to synchronize the temporal horn and strobe with the ability to mute the horn (place switches 1 and 2
w
in the ON position on the GCC24, GCCA24, GCCB24, GCCG24, GCCR24).
Mute the horn only when the temporal horn option has been selected.
w
Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.
w
Wiring for synchronized parallel (unison) horn/strobe operation.
Using this method you may:
Use four wires where two wires are used to power and synchronize the strobe and two additional wires are used to power
w
and synchronize the horn (place switches 1 and 2 in the OFF position on the GCC24, GCCA24, GCCB24, GCCG24, GCCR24).
Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns
w
with the Gentex synchronization protocol.
Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.
w
NOTICE:
w FOR THIS OPTION, SWITCHES 1 AND 2 ON THE GCC24, GCCA24, GCCB24, GCCG24, GCCR24 MUST BE IN THE OFF POSITION TO ISOLATE POWER TO THE AUDIBLE AND VISIBLE
PORTION OF THE CIRCUIT.
w ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE. THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING
SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE AND/OR MUTE THE HORN.
w REFERENCE AVSM CONTROL MODULE MANUAL (550-0284, DATED 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM MANUAL CAN BE OBTAINED AT
HTTP://WWW.GENTEX.COM OR CALL GENTEX CORPORATION AT 1-800-436-8391.
Conventional Method:
You may connect both the strobe and the horn directly from a source of rated power without the use of a control module. However, the horns and strobe lights will NOT be
synchronized. Place switches 1 and 2 in the ON position on the GCC24, GCCA24, GCCB24, GCCG24, GCCR24 to power both the audible and visible from a single pair of power wires. If
you wish to power the horn and strobe from independent sources of power, place switches 1 and 2 in the OFF position on the GCC24, GCCA24, GCCB24, GCCG24, GCCR24 and
connect power to the appropriate terminals.
UL Listed
Control Panel
First Signal
Last Signal
S+ S+
S-
H+ H-
S+ S+
Supervised
Signal Circuit
Wall Mount Horizontal Dispersion
Light
0
30
60
Light
90
% of Rating
Degrees
% of Rating
100
0
100
95
30
30
55
60
10
15
90
5
Regulated 24VFWR Max.
Operating Current (mA)
124 mA
192 mA
124 mA
192 mA
139 mA
219 mA
205 mA
286 mA
212 mA
290 mA
HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION
Horn Decibel Levels:
Reverberant Room
Minimum SPL
@ 10Ft. Per
@ 10Ft. Per
ANSI/UL 464
(HIGH)
(LOW)
83 dBA
75 dBA
81 dBA
73* dBA
86 dBA
78 dBA
84 dBA
76 dBA
UL Listed
Control Panel
S+ S+
Supervised
Signal Circuit
S-
H+ H-
E
O
L
R
Candela
15
30
75
95
115
NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS:
16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE
RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM
OPERATION.
Horn Current Ratings
Regulated 24VDC
Max. Operating
Current (mA)
HIGH Setting
23 mA
22 mA
23 mA
22 mA
First Signal
Last Signal
S-
H+ H-
S+ S+
S-
H+ H-
E
O
L
R
E
O
L
R
Models
GCSA / GCCA
GCSB / GCCB
GCSG / GCCG
GCSR / GCCR
RED Lens Strobe Current Ratings
Use with GCSR24 & GCCR24 Products
Regulated 24VDC Max.
Operating Current (mA)
124 mA
124 mA
212 mA
283 mA
313 mA
Regulated 24VFWR
24VDC Operating
Max. Operating
Current (mA)
Current (mA)
HIGH Setting
HIGH Setting
45 mA
10.8 mA
43 mA
9.3 mA
45 mA
20.7 mA
43 mA
16.5 mA
[
MAX. WIRE
APPLIANCE MIN. VOLT)
=
DISTANCE
(IN FEET)
WIRE
18 AWG
16 AWG
14 AWG
12 AWG
Includes wire to and from appliance. CAUTION: Applies only to regulated supplies.
Assumes all appliances are at the end of wire run (worse case).
CAUTION: When using only a single
power source to energize the strobe and
horn (switches 1 and 2 in the ON
position), the in/out wiring must be
under the S+ and S- terminals only.
Failure to do so may result in damage to
your signal.
Color Lens
Amber
Blue
Green
Red
Regulated 24VFWR Max.
Operating Current (mA)
192 mA
192 mA
290 mA
394 mA
414 mA
24VDC Nominal Horn
Current Rating
24VFWR Operating
Current (mA)
HIGH Setting
26.6 mA
24.4 mA
24.9 mA
38.3 mA
(PANEL VOLTAGE/
X
WIRE CONDUCTIVITY
`
TOTAL CURRENT DRAW
CONDUCTIVITY
60
95
153
244
550-0004
Page 2
[