Assembly instruction (translation)
gesis
®
NRG GST18i5
Feed-in module
• All gesisNRG system components may only be installed, commissioned and maintained by
qualified electricians.
• Personnel who install, program, operate or maintain this device must have read and
understood these instructions.
• The relevant standards, guidelines, regulations and provisions of the respective country
must be observed.
• Protective measures and mechanisms must correspond to applicable regulations.
• Damaged products may neither be installed nor operated.
• In case of a defect, please return the component to Wieland Electric.
• Never use components from third-party manufacturers. No guarantee shall be offered for
damage resulting from a combination with third-party components.
• Please keep these instructions in a safe place for later reference.
• Use only blue system components for blue flat cables (DIMM).
• Use only black system components for green and black flat cables (BASIC).
• No hazardous interchangeability with systems based on IEC 60309, IEC 60320, IEC 60906
and with national connector and socket systems for home use.
• Interchangeability between installation connector systems from different manufacturers is
not automatically prevented by compliance with EN 61535.
• Compatibility with products from other manufacturers cannot be guaranteed.
• Installation connectors do not replace national connector/socket systems for home use.
• Unused connectors must be provided with closures in easily accessible areas.
• If the feed-in module is later shifted on the flat cable, then the contact openings in the
cable must be closed with cable patch!
• Never install or remove while energized.
®
The components of the GST18
systems are used to distribute energy and/or data in building
interiors.
1
Scope of supply (pre-assembled)
The supplied components and cables may neither be changed nor modified.
• Baseplate 1x
• Equipped connecting module 1x
• Pull relief bracket 1x
• Pull relief screws 2x
• Cover 1x
2
Borehole dimensioning
3
Mounting
1.
Dismantle the feeder cable
(PE: 100 mm, L1/D1: 82 mm,
N: 72 mm, L2/D2: 62 mm,
L3: 56 mm, dismantling tool in
the cover) and strip the insulation
(8 mm). Use ferrules for fine-
stranded wires.
Insert the wires consecutively in-
to the labeled clamping points
and tighten the connection
screws (0.5 Nm).
2.
Insert the feeder cable into the
pull relief and use both screws to
tighten the pull relief bracket
(0.6 Nm).
3.
Lay the flat cable in a suitable
cable routing system. Note the
laying direction for the outlet di-
rection of the connectors. Insert
the flat cable concisely into the
coded baseplate (92.050.1553.1
for green/black cable,
92.050.163.0 for blue cable).
Doc. # BA001020 - 05/2015 (Rev. A)
®
gesis
NRG BASIC 92.050.1553.1
®
gesis
NRG DIMM 92.050.1653.0
IN FO
C A U TIO N
W A RN IN G
Wieland Electric GmbH
Brennerstraße 10 - 14
96052 Bamberg
Tél. : +49 (951) 9324-0
Fax : +49 (951) 9324-198
Internet : www.wieland-electric.com
Courriel : info@wieland-electric.com
4.
Use the two mounting holes to attach the
optional baseplate to the desired subsur-
face.
5.
Close the connecting module and latch it
with a clearly audible click. Then tighten
all of the contact screws consecutively
(0.5 Nm).
6.
Close the cover and latch it with a
clearly audible click.
Caution:
The screws are not all correctly
tightened if the cover does not
completely close!
4
Removal
1.
Use a tool (screwdriver) to open
the cover interlock. Press the in-
terlock lugs in the direction of the
arrow.
2.
Loosen the contact screws and
connection screws.
3.
Use a tool (screwdriver) to
unlatch the baseplate interlock
and to release the module from
the flat cable. Use cable patch to
seal openings in the insulation.
5
Technical data
Rated voltage
250 / 400 V
Rated current
20 A
Protection class
I
Protection type
IP40
Connector cross section
f with ferrules
2.5 ̶ 4 mm²
of feeder cable
Caution:
Ferrules must be used for fine-wired cables!
Tightening moment of
0.5 Nm
the contact screws
Tightening moment of
0.6 Nm
the pull relief
gesis
®
NRG GST18i5
e without ferrules
2.5 ̶ 6 mm²
EN