4.1
Function
The burner pump sucks the liquid fuel from the tank via the filter insert. The
fuel not burnt by the burner nozzle is returned to the vent via the return line
and then resupplied to the burner via the flow line. Only the amount of fuel
actually burnt is taken from the tank and added to the de-aerated fuel.
A
4.2
Approvals, conformities, certifications
The product is TÜV-tested (report number 968/FSP 2170.01/21).
4.3
Technical data
Parameter
General specifications
Dimensions (W x H x D)
with short filter cup
Connection burner
Flow and return
Connection tank
Nozzle capacity
Return flow
Separating capacity air/gas, depend-
ing on air content of fuel
Mounting position
Operating overpressure
Suction pressure
Test pressure
Product description
B
C
D
A. Q
= Q
Tank
B. Q
Return
C. Q
Flow
D. Q
Nozzle
Value
165 x 221 x 98 mm
G3/8 male with 60° cone for burner
hose
G3/8 female at shut-off valve
Max. 100 l/h
Max. 120 l/h
> 4 l/h (de-aeration unit only)
> 6 l/h (as per EN 12514-3)
Float housing vertical to the top
Max. 0.7 bar (corresponds to a
static liquid column of approxi-
mately 8 m)
Max. -0.5 bar
6 bar
FloCo-Top-1K
EN
Nozzle
8