Installing cables
– Strip the ends of the cables as follows:
Cable cross-section
6 mm²
10 mm², 16 mm²
Ø 0 .8 mm
– Perforate the plug-in seals with cables and insert them
into the FireBox in such a way that the cable sheath
protrudes approx . 10 mm into the housing (Figure
– Insert the cable into the FireBox and screw the ends
into the terminals .
Danger! Electric shock!
If there is a fault when working in the housing, the
metal rail of the connection unit may cause an
electric shock . Observe the following step:
– Always place the protective conductor (power supply)
or shield (data cable) on the yellow and green PE
terminal .
– Using clips, fasten the cable running to the FireBox at
a spacing of max . 100 mm (Figure
The rigid cable fastening between the FireBox terminals
and clips should prevent sagging and, in case of fire,
prevent the creation of short-circuits .
– Attach the lid and lock it by turning the four corner
screws through 90° (Figure
– Write on the identification plate (accessories) and
a ttach it .
12
Stripping length
7 mm
10 mm
6 mm
7
) .
8
) .
6
) .