LN INTERFACE
The following describes a connection example on the system.
Terminator resistor setting
TCC-LINK terminator resistor
The TCC-LINK terminator resistor is set on the air conditioner side.
(See "6 Setting" for setting.)
LON terminator resistor
The L
terminator resistor is set on the upper L
ON
Shield grounding of communication cables
TCC-LINK communication cable
Do not connect the shield wire to the terminal block. It should be open and insulated. The TCC-LINK
communication cable must be earthed on the air conditioner.
communication cable
L
W
®
ON
ORKS
Do not connect the shield wire to the terminal block. It should be open and insulated. Connect the shield wire of
the L
W
communication cable to the earth on the upper system side.
ON
ORKS
Building management
system
(by other company)
(Other company's
system)
Do not connect the shield wire
to the terminal block
The LON terminator resistor is
set on the upper L
W
ON
ORKS
system side. Do not set it here.
Power supply
220 - 240 VAC
W
ON
ORKS
Do not connect the
shield wire to the
terminal block
SW5
®
LN interface
®
system side.
The TCC-LINK
Set (maximum -1)
terminator resistor
of the indoor unit
is set on the air
central control
conditioner side.
address with SW1
Set SW5 to OFF.
and SW2 in
hexadecimal
number.
TCC-LINK main bus
Outdoor
U4 U3
unit
SW1
SW2
U2 U1
U2 U1
Indoor
unit
Remote
controller
– 6 –
Installation Manual
Outdoor
U4 U3
U4 U3
unit
Central
U2 U1
remote
controller
U2 U1
U2 U1
Indoor
Indoor unit
unit
Remote
controller
6-EN