Technical Specifications - toscano Vigilec V1z Guide D'utilisation

Coffret digital de commande et protection pour 1 pompe jusqu'à 18 a, 230 v ou 400 v ac, multi-contrôle
Masquer les pouces Voir aussi pour Vigilec V1z:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8. TECHNICAL SPECIFICATIONS

Supply Voltage
Motor current range
Protections
Level control
Inhibition time (flow detector)
Underload setting
Overload setting
Restart time
Control voltage (probes/floats)
External control (EXT. ON/OFF)
Terminal blocks wiring size
Cable glands
Recording information
(PUMPCHECK)
Size*/Weight/IP/Temperature
*HEIGHTxWIDTHxDEPTH
24
230 V AC or 400 V AC (depending on model) / -20%...+30% /
50/60Hz
0,5.....18 A / AC3
Underload, overload, phase failure and over-voltage
Two probes, timed probe, no probes or flow switch
Selectable in 15, 30, 60, or 90 seconds
OFF - 0,5... 21 A (jump in 4 seconds)
0,5...21 A (jump in 7 seconds)
Disabled (OFF) or adjustable from 3 minutes up to 8 hours
12 V AC
Dry contact or voltage from 6 to 24 V AC/DC
10 mm² (power) / 4 mm² (control)
Supply and Pump: 2xM20 / Control: 2xM16
Module identification number, pump running hours, pump
starts, pump alarms and last alarm trip current
240 x 190 x 110 mm / 1,82 kg / IP65 / -10...+55 ºC

Hide quick links:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vigilec zero v1z