Installing The Outdoor Unit; Installing The Refrigerant Piping - Mitsubishi Electric PUHZ-SWHA Série Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21

3. Installing the outdoor unit

A M10 (3/8") bolt
B Base
C As long as possible.
D Vent
E Set deep in the ground
SW50
SW50
500
Min. 650
500
Min. 350
154.5
154.5
809

4. Installing the refrigerant piping

4.1. Precautions for devices that use R410A refrigerant
• Refer to 1.4. for precautions not included below on using outdoor units with
R410A refrigerant.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil
applied to the fl ared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specifi ed in the table to the below. Make sure the insides of the pipes are clean
and do not contain any harmful contaminants such as sulfuric compounds,
oxidants, debris, or dust.
Always apply no-oxidation brazing when brazing the pipes, otherwise, the
compressor will be damaged.
(mm)
B
SW75-120
SW75-120
Min. 360
600
600
Min. 10
175
950
Fig. 3-1
• Be sure to install the unit in a sturdy, level surface to prevent rattling noises during
operation. (Fig. 3-1)
<Foundation specifi cations>
Foundation bolt
Thickness of concrete
Length of bolt
Weight-bearing capacity
• Make sure that the length of the foundation bolt is within 30 mm of the bottom
surface of the base.
• Secure the base of the unit fi rmly with four-M10 foundation bolts in sturdy loca-
tions.
Installing the outdoor unit
• Do not block the vent. If the vent is blocked, operation will be hindered and break-
down may result.
• In addition to the unit base, use the installation holes on the back of the unit to
attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15
mm or less) and install on site.
Warning:
• The unit must be securely installed on a structure that can sustain its
weight. If the unit is mounted on an unstable structure, it may fall down and
cause damage or injuries.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.
175
Warning:
When installing or relocating, or servicing the outdoor unit, use only the speci-
fi ed refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any
other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other haz-
ards.
The use of any refrigerant other than that specifi ed for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
Pipe size (mm)
[6.35 [9.52 [12.7 [15.88 [19.05 [22.2 [25.4 [28.58
Thickness (mm)
0.8
0.8
• Do not use pipes thinner than those specifi ed above.
• Use 1/2 H or H pipes if the diameter is 22.2 mm or larger.
M10 (3/8")
120 mm
70 mm
320 kg
0.8
1.0
1.0
1.0
1.0
1.0
5

Publicité

Table des Matières
loading

Table des Matières