avoid the hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than
the UPS's maximum input current. Otherwise the receptacle may be burned and destroyed.
9) Switch off the mains switch in the building before installation.
10) Turn off all the connected devices before connecting to the UPS.
11) Prepare wires based on the following table:
Model
E4 LCD Evolution 5K / 6K
E4 LCD Evolution 5K S / 6K S
E4 LCD Evolution 10K
E4 LCD Evolution 10K S
NOTE 1: The cable for 6K/6KL should be able to withstand over 40A current. It is recommended to
use 10AWG or thicker wire for safety and efficiency.
NOTE 2: The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to
use 8AWG or thicker wire for safety and efficiency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and
regulations.
12) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the
following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect
the earth wire last when making wire disconnection!)
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 14 AA 59 203 45
Wiring spec (AWG)
Input
Output
Battery
6 / 10
6 / 10
6 / 10
6 / 10
10 / 8
10 / 8
10 / 8
10 / 8
Ground
6 / 10
6 / 10
6 / 10
10 / 8
10 / 8
10 / 8