Operation
The JAGUAR contains an internal sensor that will automatically start the pump when
condensate is detected and stop the pump when the condensate has been removed.
The JAGUAR is also fitted with a high water level alarm that will operate the alarm relay
if the water level rises to abnormal levels. The pump will continue to run until the
minimum water level is reached and the alarm will reset.
Installation
The JAGUAR pump can be installed at any angle between horizontal and vertical so long
as the breather tube inlet is above the condensate inlet (Fig. 3). The JAGUAR can also be
tilted sideways up to 30° from horizontal (Fig. 2).
30°
Fig.2.
The JAGUAR pump should be positioned in a suitable location within the equipment
below the level of the collection tray. The top of the breather tube should be positioned
above the highest part of the collection tray to avoid overflowing (Fig. 4). The JAGUAR
pump, condensate tubes and mains cable should be kept away from panels and surfaces
and, where possible, insulated with foam to minimise noise.
Drain hose
Inlet connector
Outlet
Fig.1.
30°
Breather support
Breather tube
Inlet
Inlet
connector
90°
Foam insulation
GB
Fig.3.
Fig.4.
3