The PANTHER is a self-contained
condensate removal system for use
directly inside trunking and high-
wall-mount air conditioners.The
small remote sensor can be fitted
inside the air handler whilst the
pump unit can be positioned
elsewhere.
Specifications
Power supply:
Power consumption:
Alarm relay:
Capacity:
Maximum head:
Ambient temp:
Water temp:
Material:
Discharge tube:
Dimensions:
IP:
12
3
11
10
9
8
2
7
6
5
4
1
3
2
1
0
0
0
1
1
0
120/240Vac, 50/60Hz Auto sensing
16W max., 0.25W when idle
5A, 30Vdc, 250Vac Break on fault
12 litres/hour max. (3.17 US gal/h)
Vertical >20m (65 ft), Horizontal >100 m (328 ft)
Suction 1 m max. (3.28 ft)
0 - 40°C
25°C max.
Flame retardant ABS UL94 5VA
6mm (1/4") ID
Pump:
135 x 46 x 32mm (5.3" x 1.8" x 1.26")
Sensor: 45 x 36mm dia. (1.8" x 1.4" dia.)
20
2
3
4
5
6
7
8
10
20
PANTHER
Condensate removal pump
Installation and operating guide
Capacity
9
10 11 12 13 14
15
30
40
Vertical lift
0m Horiz
50m Horiz
100m Horiz
(m)
16 17 18 19 20
(ft)
50