CD5.241-L1 Installation Manual
EN
Product Description
The CD5.241-L1 is a DIN-rail mountable DC/DC converter, which provides a floating, stabilized and
galvanically separated SELV/PELV output voltage.
The output of the device fulfills the requirements for a limited power source according to NEC Class 2.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as in
industrial control, process control, monitoring and measurement equipment or the like. Do not use this
device in equipment where malfunction may cause severe personal injury or threaten human life.
If this device is used in a manner outside of its specification, the protection provided by the device may
be impaired.
Installation Instructions
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the
device. Other mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide
protection against spilled liquids.
The isolation of the device is designed to withstand impulse voltages of 1.5kV according to IEC 60664-
1.
The input can be powered from batteries or similar DC sources. The voltage between the input
terminals and ground must not exceed 60Vdc continuously. The ripple voltage in the low frequency
range between 50Hz and 10kHz must be negligible when used in marine applications.
The input must be powered from a PELV or SELV source or an "Isolated Secondary Circuit" in order to
maintain a SELV or PELV output.
Check for correct input polarity. The device will not operate when the voltage is reversed.
A disconnecting means shall be provided for the input of the device.
The device is designed as "Class of Protection III" equipment according to IEC 61140. A PE (ground)
connection is not required. However, connecting the chassis ground terminal to ground can be
beneficial to gain a high EMI immunity.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in
output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device
is permanently loaded with less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 50A without additional protection
device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or 8A C-
Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II
Category 3 (Zone 2) environments.
Classification: ATEX: EPS 08 ATEX 1 142 X, II 3G EX ec nC IIC T4 Gc / IECEx EPS 14.0001X
WARNING EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment.
Do not disconnect the device unless power has been switched off or the area is known to be non-
hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54
and fulfils the requirements of the EN 60079-0.
Reduced output current conditions must be considered for high ambient temperatures and non-
standard mounting orientations.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including unlimited inductive and capacitive loads.
Do not apply return voltages from the load to the output terminals higher than 30V.
The green DC-OK LED reports a voltage on the output terminals above 21Vdc, which is produced by the
device itself.
The device is equipped with an over-temperature protection. In case of a high temperature, the output
shuts down and starts automatically again after cooling off.
Do not connect outputs of devices in a parallel connection for higher output currents.
Do not connect outputs of devices in a series connection for higher output voltages.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32.0V. The
output shuts down and automatically attempts to restart.
Technical Data
All values are typical figures specified at 24Vdc input voltage, 24V, 3.8A
output load, 25°C ambient and after a 5 minutes run-in time unless
otherwise noted.
Output voltage
DC 24V
Adjustment range
24Vdc
Output current
3.8A
Input voltage
DC 24V
Input current
4.25A
Input inrush current
1.2A pk
Efficiency
90.5%
Power losses
9.7W
Hold-up time
7ms
Temperature range
-25°C to +70°C
Max. wire size (litz wire)
4mm²
Wire size AWG
AWG 20-10
Max. wire diameter
2.8mm
Wire stripping length
10mm / 0.4inch
Size (wxhxd)
32x124x102mm
Weight
425g / 0.94lb
Functional Diagram
+
Reverse
Input
Polarity
Fuse
Power
Protection
-
&
Converter
&
Input
Inrush
Filter
Limiter
Chassis
Ground
Output
Voltage
Protection
Output Characteristic
Output voltage
28V
24V
12V
0V
0A
1A
2A
3A
Temperature Range
Allowed output current at 24V
3.8A
3.0A
2.0A
1.0A
0A
-25
0
+25
Nominal
Below +70°C ambient
-40% / +35%
Temp. independent
For all terminals
For all terminals
For all terminals
For all terminals
Without DIN-rail
+
+
Output
Filter
-
-
Over-
DC-
OK
4A
5A
6A
Output current
+45
+60
+70°C
Ambient temperature