TROUBLESHOOTING
UNIPOWER 1000.12Q / UNIPOWER 1000.24Q / UNIPOWER 600.12P / UNIPOWER 1200.12P
Troubleshooting
Sound alarm
Unipower does not deliver current
anymore
Causes
Discharged battery
24V>230V inverter :
battery not suitable (12V
instead of 24V)
Battery/inverter connection is
defective
The inverter is off
Battery connection problem
Thermal protection : the inner
temperature of the inverter is
above 45°C
Overconsumption
Inverter/devices to supply
connection problem
.
WWW
UNITECK
Remedies
Recharge your battery or
replace it, if it is defective.
Replace your 12V battery by a
24V battery.
Check your connections
(cables, terminals,
tightening...)
Put it on again.
Check your battery
connections.
Stop the consumer. Let the
inverter cool down and improve
the ventilation.
Recharge your battery.
Unipower will restart when the
battery
voltage
acceptable.
Replace the battery if
necessary.
Check the connections.
.