4.2 TECHNICAL SPECIFICATIONS

2
The specifications directly referred to the unit purchased are indicated on the identification
tag located in the internal side of the machine (see Fig. 1). Technical specifications (standard)
3
concerning installation and use of the fan coil units are listed on Enclosures 2 and 3 of this
manual.
4
5
6
Fig. 1 Label on Sphera
7
• Insulation class: I
• Protection grade: IPX0
• External structure in ABS thermoplastic material
8
• Technical features of the heat exchanger:
-
Max pressure of the hot or cold water for water fan coil:
1600 kPa - with valves: 1000 kPa
9
-
Min pressure of the hot or cold fluid: It is the one indicated by the designer/installer for
the correct functioning of the system
Min/max water temperature: 5/85 °C
-
10
-
Hardness of water into the heat exchanger: It is the one indicated by the de-
signer/installer for the correct functioning of the system
-
Water flow: see Enclosure 3
+
• Technical features of the fan motor:
-
With each fan coil unit there is the possibility to have 6 different air volumes and
the relevant electric motor connections accordingly to the use requirements. The
standard electrical connection has a triad of speeds: MIN-MED-MAX (size 20: L-6,
L-4, L-1 and size 40: L5, L2, L1). The relevant nominal air capacities are indicated
in the Encl. 3 and they are referred to standard fan coil units, with clean filters, at
the temperature of 20 °C, at sea level and without external static pressure.
-
The electric motor is provided with internal thermic protection; it is a monophasic
motor with capacitor permanently inserted.