The load does not turn OFF after sensor time delay expires.
• Hold ON input is active.
• Check sensitivity on the occupancy sensor.
• Verify that the time amount is the intended amount.
• Verify that the sensor is not being retriggered by unintentional movement or byplacement too close to a an air vent.
The load does not respond when I press the momentary switch.
• Check wiring.
The load does not come on automatically although the Mode Switch is set to Auto ON.
• Cycle power to the unit to reset operating mode to Auto ON. Mode Switch location was changed while the power pack was powered
(line voltage).
The load comes on automatically with occupancy although the Mode Switch is set to Manual ON.
• Cycle power to the unit to reset operating mode to Manual ON. Mode Switch location was changed while the power pack was
powered (line voltage).
No LED activity as described above.
• Check for excessive load.
• Check AC power.
Description
Power Pack
Input Voltage
120—277 VAC, 50/60
Hz, single-phase
Ballast (A)
20
Incandescent
20
(A)
Motor (hp)
1
Plug Load
20 A, 120/240 VAC
Output
24 VDC, 225 mA
w/relay connected
Auto/Manual-ON
No
Slide Switch
Control ON
Yes
Hold ON
No
Hold OFF
No
Manual ON/
No
OFF
Override
Yes
Button
Power Loss Mode
No
ORDERING INFORMATION
BZ-200
Power Pack
120—277 VAC, 50/60 Hz,
single-phase
20
20
1
20 A, 120/240 VAC
24 VDC, 225 mA
Yes
Yes
Yes
Yes
Yes
Yes
Yes
BZ-250
BZ-250-347
Power Pack
120—347 VAC, 50/60
Hz, single-phase
16
16
1/4
15A, 120/240 VAC
24 VDC, 225 mA
Yes
Yes
Yes
Yes
Yes
Yes
Yes
5