Manuel d'utilisation
Aquavision control
Module de surveillance
Register 30013
Register 30014
Register 30015
Register 30016
Register 30019
Register 30020
Register 30021
Register 30022
Register 30025
Register 30026
Register 30027
Register 30028
Register 30031
Register 30032
Register 30033
Register 30034
Register 30035
Register 30036
Register 30037
Register 30038
Register 30039
Register 30040
Register 30041
Register 30042
Register 30043
Register 30044
Register 30045
Register 30046
Register 40001
Register 40002
Register 40003
Register 40004
Register 40005
Pour connaître la valeur totale de la consommation d'eau dans un circuit, faites le calcul suivant:
Valeur registre (low word) + valeur registre (high word)*65.535)
18/20
www.cadis.be
Sub Watermeter 1 Total Low Word
Sub Watermeter 1 Total High Word
Sub watermeter 1 Current flow Low word
Sub watermeter 1 Current flow High word
Sub Watermeter 2 Total Low Word
Sub Watermeter 2 Total High Word
Sub watermeter 2 Current flow Low word
Sub watermeter 2 Current flow High word
Sub Watermeter 3 Total Low Word
Sub Watermeter 3 Total High Word
Sub watermeter 3 Current flow Low word
Sub watermeter 3 Current flow High word
Actual Temperature in °C *10
Actual Pressure in Bar *10
Valve status Sub watermeter 1
Valve status Sub watermeter 2
Valve status Sub watermeter 3
Status External command for Unlimited mode
Status External leak input
Status External Burgalarm Input
Time left in hours untill Unlimited mode ends
General Status AquaControl
Alarm SuB Watermeter 1
Alarm SuB Watermeter 2
Alarm SuB Watermeter 3
Alarm between Street watermeter and official watermeter
distribution company
Alarm Temperature Sensor Out of range
Alarm Pressure Sensor Out of range
Low temperature limit in °C * 10
High temperature limit in °C * 10
Low pressure limit in °C * 10
High pressure limit in °C * 10
Start Unlimited mode for 24 hours
info@cadis.be
1 = Valve closed/0= Valve open
1 = Valve closed/0= Valve open
1 = Valve closed/0= Valve open
1 = Input closed/0 = Input open
1 = Input closed/0 = Input open
1 = Input closed/0 = Input open
Value in hours (0 - 24)
1 = Alarm/0 = System normal
1 = Sub watermeter 1 alarm/ 0 =
System normal
1 = Sub watermeter 2 alarm/ 0 =
System normal
1 = Sub watermeter 3 alarm / 0 =
System normal
1 = Alarm / 0 = System normal
1 = Sensor alarm/0 = Sensor normal