Switching Output Characteristics / Adjustment Conditions - Rechner Sensors i-level+ Notice D'utilisation

Avec 1 ou 2 seuils complémentaires
Masquer les pouces Voir aussi pour i-level+:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Switching output characteristics
The probe needs 2 seconds for initialization when power is switched on. The probe is supplied without any
preset switching points. Therefore all outputs are in OFF mode. During initialization the ETW input and the
outputs are inactive.
Please note:
The measuring mode is inactive during the adjustment.
Output characteristics KFW-51...ETW (1 switching point):
A1 = OFF, no reaction on the filling level g no adjustment for S1 or the adjustment was not successful (error!)
A1 = Alternating with 15 Hz frequency g Adjustment of S1 active
A1 = Alternating with 0.4 Hz frequency g Output test function
A1 = Reaction on the filling level g S1 is adjusted.
Output characteristics KFW-52...ETW (2 switching points):
A1 = OFF, no reaction on the filling level g no adjustment for S1 or the adjustment was not successful (error!)
A2 = OFF, no reaction on the filling level g no adjustment for S2 or the adjustment was not successful (error!)
A1 = Alternating with 15 Hz frequency g Adjustment of S1 active
A2 = Alternating with 15 Hz frequency g Adjustment of S2 active
A1 = Alternating with 0.4 Hz frequency g Output test function
A2 = Alternating with 0.4 Hz frequency g Output test function
A1 = Reaction on the filling level g S1 is adjusted
A2 = Reaction on the filling level g S2 is adjusted
Adjustment conditions KFW-52...ETW
• The switching points are totally independent from each other. The adjustment of S1 has no influence to
S2 or vice versa.
• There is no hierarchy to be considered.
• With the reset all switching point adjustments are cancelled.
27

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Kfi-5-1 etw sérieKfi-5-12 etw série

Table des Matières