Installation
Terminal Parameter
12, 13
3
3
18
19
32
33
27
29
20
39
42
50
53
54
55
61
68 (+)
69 (-)
10
Terminal Description
Digital Inputs/Outputs
Default
Setting
Description
-
+24V DC
24V DC supply
voltage. Maximum
output current is
200mA total for all
24V loads. Useable for
digital inputs and
external transducers.
E-01
[8] Start
E-02
[0] No
operation
E-05
[0] No
Digital inputs.
operation
E-06
[0] No
operation
E-03
[0] No
Selectable for either
operation
digital input or
output. Default setting
E-04
[14] JOG
is input.
-
Common for digital
inputs and 0V
potential for 24V
supply.
Analog Inputs/Outputs
-
Common for analog
output
AN-50
Speed 0 -
Programmable analog
High Limit
output. The analog
signal is 0–20mA or
4–20mA at a
maximum of 500Ω
-
+10V DC
10V DC analog supply
voltage. 15mA
maximum commonly
used for potenti-
ometer or thermistor.
AN-1#
Reference
Analog input.
Selectable for voltage
AN-2#
Feedback
or current. Switches
A53 and A54 select
mA or V.
-
Common for analog
input
Serial Communication
-
Integrated RC filter for
cable shield. ONLY for
connecting the shield
when experiencing
EMC problems.
O-3#
RS-485 Interface. A
control card switch is
O-3#
provided for
termination resistance.
AF-600 FP Quick Guide
Terminal Parameter
01, 02, 03
04, 05, 06
Table 3.2 Terminal Description
3.4.5.3 Wiring to Control Terminals
Control terminal connectors can be unplugged from the
drive for ease of installation, as shown in Illustration 3.12.
Illustration 3.12 Unplugging Control Terminals
1.
2.
3.
4.
Illustration 3.13 Connecting Control Wiring
DET-759A
Terminal Description
Digital Inputs/Outputs
Default
Setting
Relays
E-24 [0]
[0] Alarm
E-24 [1]
[0] Running
Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in Illustration 3.13.
Insert the bared control wire into the contact.
Remove the screwdriver to fasten the control wire
into the contact.
Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
Description
Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.