19
7. GENERAL DATA
Dimensions
and weight
Supply
network
Motor
connection
Ambient
conditions
EMC
Standards
Certificates
and
manufacturer's
declarations of
conformity
General Data
Frame
Height Width Depth (mm) Weight (kg)
MI1
156,5
MI2
195
MI3
262,5
SmartDrive Compact cannot be used with corner
grounded networks
Output voltage
0 - U
Output current
Continuous rated current I
ture max. +50ºC, overload 1.5 x I
10min
Ambient operating
-10°C (no frost)...+50°C: rated loadability I
temperature
Storage
-40°C...+70°C
temperature
Enclosure class
IP20
Relative humidity
0...95% RH, non-condensing, non-corrosive, no
dripping water
Altitude
100% load capacity (no derating) up to 1000m.
1% derating for each 100m above 1000m; max.
2000m
Immunity
Complies with EN50082-1, -2, EN61800-3
Emissions
Complies as standard with EN6 1800-3 Cate-
gory C2 (Honeywell level H: normal public elec-
tricity network requirements). Category C1 with
external EMC-filter (Honeywell level C: special
requirements for sensitive areas installations).
For EMC: EN61800-3,
For safety: UL508C, EN61800-5-1
For safety: CB, CE, UL, cUL,
For EMC: CE, CB, c-tick
(see unit nameplate for more detailed approvals)
65,5
98,5
90
101,5
100
108,5
in
N
Honeywell
0,55
0,70
0,99
at ambient tempera-
max. 1min/
N
N
7-EN