3.3.8 Thermal compensation
STP-UNI-2.8 and STP-UNI-5.0 temperature probes enable the compensation of Absorption voltage and Floating
Voltage depending on the ambient temperature of the battery room.
The coefficient used is -18mV/°C for 12V model and -36mV/°C for 24V models
Temperature is not compensated when Wintering (or standby sealed bat), Stabilized DC power supply and Lithium Iron
Phosphate (LiFePO4) with BMS settings are selected
3.3.9 CAN Bus
The battery charger offers two receptacles matching with connectors Molex Microfit 3.0, 6 circuits (reference 43025-
0600).
Documentation n° 1336205REG_CAN (hardware and software specification) is available upon request.
3.3.10 Remote display
The battery charger supports the remote tactile colour display UNI-DISPLAY-R.
3.3.11 Remote control
This option G-ON/OFF-R allows you to shut down the remote charger from a two-wire cable.
The converter is stopped if both wires are short-circuited
3.3.12 Factory setting
The charger's factory settings are: sealed Lead, BOOT ON
This setting is a compromise for satisfactory recharging of different technologies of battery:
-
Opened classic lead
-
Sealed, Gel or AGM
-
Spiral sealed
-
Lithium Iron Phosphate ( LiFePO4 ) with BMS
To define the charge in function of your battery, please refer to the chart, paragraph : 3.3.2.
For special batteries, call in a professional installer, who will make the specific settings in accordance with the battery
manufacturer's specifications and according to the specifics of the installation.
CRISTEC is not liable for any damage caused to the batteries or for inefficient recharging.
35