CSA Installation drawing 6333QC02-V2R0
For safe installation of the single channel 6333A1A or the two channel 6333A1B
the following must be observed. The module shall only be Installed by qualified
personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
Marking
Class I, Division 2, Group A,B,C,D T6...T4
Ex nA[ic] IIC T6...T4
Class I Zone 2 AEx nA[ic] IIC T6...T4
Terminal: 41,42,43,44
Uo: 5 VDC
Io: 4 mA
Po: 20 mW
Lo: 900 mH
Co: 1000 μF
Terminal:
51,52,53,54
Uo: 5 VDC
Io: 4 mA
Po: 20 mW
Lo: 900 mH
Co: 1000μF
T4: -40ºC to 85 ºC
T6: -40ºC to 60 ºC
44
+
43
13
-
42
11
41
CH1
54
+
53
23
-
52
21
51
CH2
6333V108-FR
Hazardous Area
CL I, Div 2, GP ABCD
CL I, Zone 2, IIC
Terminal:
11-13
Functional Ratings:
U nominal ≤ 35 VDC;
I nominal ≤ 3.5 - 23 mA
Terminal:
21-23
Functional Ratings:
U nominal ≤ 35 VDC;
I nominal ≤ 3.5 - 23 mA