Description of redundancy
LD-64D is connected through two parallel fibre optical rings, ring 1 and ring 2. The ring
topology introduces the possibility for the units to handle a fault on a fibre or a fibre pair
and still maintain communication. The units will automatically change the communication
path when a fault is detected. This change can take up to 4 ms and all data sent during
this time needs to be resent since the modems do not have any possibility to databuffer.
One modem in the ring needs to be configured as master through switches inside the
unit. The master controls the data and prevents data to be resent through the ring. The
master is also used for monitoring of the fibre rings since all faults detected in the rings
will be sent to the master. This gives possibility to monitor the complete system through
the master unit. The other modems in the ring needs to be configured as slaves and will
be transparent during normal communication.
LD-64D is equipped with alarm signals which is used for indication of fibre interruptions.
Each unit is equipped with two alarm ports, one for each fibre channel. These ports are
marked as CE1 and CE2 on the unit. A fault will close the circuit between indications
"C" and "E" on respective port. The alarm outputs can for example be used for
connection of an external relay. See connection and examples on page 19–20.
An interruption will be detected by the closest unit which will indicate a receiver alarm
and also send the error further to the master unit which will indicate a corresponding
fault for the ring.
For correct function the fibre optic rings needs to be connected correct between
each modem
Ring 1: Tx1 – Rx2 – Tx1 – Rx2 etc.
Ring 2: Tx2 – Rx1 – Tx2 – Rx1 etc.