en
|
Technical data
Ingress protection:
Mounting bracket
Support fixing:
Vertical adjustment range:
Horizontal adjustment range:
Environmental specification
Operation ambient temperature:
Storage ambient temperature:
Relative humidity:
Operation specification
Detector range (depth of field):
Sensitivity range:
Detector response time:
Horizontal field of view:
Vertical field of view:
Alarm setting:
Self-test facility:
Heated optics
LED status
Output options:
Relay:
16
IP66 & IP67 (NEMA 4X &6P)
M8 (quantity 2)
0° - 45°
±45°
-60 °C to +85 °C (-76 °F to +185 °F)
-60 °C to +85 °C (-76 °F to +185 °F)
0-100 % (non-condensing)
2 m to 39 m (6 ft to 127 ft)
Low, Standard (Factory default) and
High
4 s - 30 s
100°
80°
Non-latching with automatic reset
after 15 s (default) OR Latched until
the power is removed from detector.
Yes – no mirror continuous automatic
optical verification
Yes
Tri-state LED
®
0(4) - 20 mA, HART
7, Relay con-
tacts - alarm and fault
2 Relay Contacts – Alarm and Fault.
SPST, 2 A @ 30 Vdc
Communication/Configuration:
RFI/EMC:
Power on reset delay:
10
Order list
Description
Dräger Flame 1350 variants
2 x M25, aluminium
2 x M25, stainless steel
2 x 3/4" NPT, aluminium
2 x 3/4" NPT, stainless steel
Flame simulator
Dräger Flame Simulator FS-5000
Accessories
Bracket standard, 316 stainless steel
Bracket marine, 316 stainless steel
Sunshield, Flame 1x00/3x00/5x00
Mount kit, 2" pole
Mount kit, 3" pole
Mount kit, 4" pole
Sealing kit detector, metric
Additional cable entry variants available upon request.
®
RS485 and HART
7
Complies with IEC 61000
5 s
Part number
3724443
3724442
3724441
3724440
4209307
3718732
3701298
3701299
3701300
3701301
3701302
3701303
Instructions for use
|