Télécharger Imprimer la page

Comfort Glow CGWF4000 Manuel D'installation Et D'opération page 17

Publicité

OPERATION
your stoves efficiency and leads to accelerated
creosote buildup in your chimney. Be considerate of the
environment and only burn dry wood.
CAUTION:
DO NOT LEAVE APPLIANCE UNATTENDED WITH
THE DOOR OPEN.
WARNINGS:
• NEVER OVERFIRE YOUR STOVE. IF ANY PART
OF THE STOVE STARTS TO GLOW RED, OVER
FIRING IS HAPPENING. READJUST THE AIR
INTAKE CONTROL AT A LOWER SETTING.
• THE INSTALLATION OF A LOG CRADLE OR
GRATES IS NOT RECOMMENDED IN YOUR WOOD
STOVE. BUILD FIRE DIRECTLY ON FIREBRICK.
• NEVER PUT WOOD ABOVE THE FIREBRICK
LINING OF THE FIREBOX.
• ATTEMPTS
TO
RATES
THAT
EXCEED
SPECIFICATIONS CAN RESULT IN PERMANENT
DAMAGE TO THE FURNACE.
GENERAL FURNACE OPERATION
Honeywell Limit Control
This device, mounted in the ductwork, just above the air
discharge atop the furnace, works in conjunction with
a wall thermostat, operating the distribution blowers
and the combustion fan on the rear of the furnace. The
factory settings are 100/150/200. The wall thermostat
setting operates the ON time of the combustion fan. If the
temperature is below the setting on the wall thermostat,
the combustion fan will come ON (recommended
setting at 5 to 10 degrees higher than other heating
thermostats.) The first two set points on the limit control
operates the distribution blowers. When the furnace
plenum temperature reaches the second set point on the
limit control, the distribution blowers will come on. If the
temperature falls to the first set point, the distribution
blower will shut-off. When the furnace reaches the
third set point on the limit control, the combustion fan
will shut-off. Once the temperature falls below that set
point and the wall thermostat is still calling for heat, the
combustion fan will turn back on. The 200° is a factory
preset limit for the combustion fan and should never
be changed. Doing so could result in excessive firebox
temperatures and could permanently damage your
firebox.
ACHIEVE
HEAT
OUTPUT
FURNACE
DESIGN
FURNACE LOADING PROCEDURE
Starting your Furnace
1.
Ensure that the wall thermostat is set to its maximum
setting and your combustion fan is running on the
rear of the furnace.
2. Close the spin damper on the combustion fan and
adjust the barometric damper on the front of the
furnace to OPEN by moving the knob down and
shifting it into the lower slot.
AUTO
OPEN
3. Start the fire with approximately 12 lbs. of kindling,
which will be several small strips of wood, 1-1/2 to
2-1/2 inches wide, approximately 12 to 15 inches
deep in the bottom of the firebox. Leave the fuel
loading door slightly open to ensure good ignition of
the kindling. Make sure the combustion fan is ON and
its damper is closed, then adjust the knob to OPEN
the barometric damper.
17
OPEN

Publicité

loading