ENGLISH
MAINTENANCE
Maintenance and inspection of this product must be carried
out in accordance with EN 12056-4. To ensure continued reli-
ability of service, we recommend that you take out a service
contract.
NOTICE! The maintenance of the sewage lifting station and
maintenance measures are carried out by specialists at inter-
vals of 3 months in commercial premises, multi-family homes
in 6 months or 12 months in family homes.
WARNING!
Before carrying out any works: disconnect the pump and the
controls from the mains and take steps to ensure that they
cannot be energized again.
WARNING!
Check the cable for mechanical or chemical damage. Damaged
or kinked cables must be replaced by the manufacturer.
We recommend that the following works be included in the
service:
1. Check the connection points for watertightness and in-
spect the areas surrounding the unit and the fittings.
2. Operate the shut-off valves and check that they move eas-
ily. Adjust and grease them if necessary.
3. Open and clean the swing-type check valve; check the seat
and valve (ball)
4. Clean the pump and the pipes where they connect to the
unit; check the impeller and the bearings.
CAUTION!
Worn impellers can have sharp edges.
5. Oil check. If necessary top up or change oil (if oil chamber
available).
6. Clean the inside of the tank (as necessary, or if especially
required); remove any grease, for example.
7. Check the condition of the collecting tank.
8. Flush the system through with water once every 2 years.
9. Inspect the electrical section of the unit. The control unit
itself is maintenance-free, but if a rechargeable battery is
fitted, then it should be checked regularly to ensure that it
is in good working order. To do so, unplug the unit from the
mains and lift the float of the level controller slowly by hand
and hold it there until the alarm is triggered.
10. In addition, clean the float if necessary.
When all the servicing tasks have been performed, carry out a
test run and then put the unit back into operation. The service
must be documented, giving details of the important data and
of all the tasks carried out.
WARNING!
Compli 1015/4 BW S1 | 1025/4 BW S1
Burns from hot oil!
Motor housing is filled with oil! The motor housing must be
drained before disassembly.
Motor housing may be pressurised. Be careful when removing
the oil plug.
22
QUICK TIPS FOR REMEDYING FAULTS
WARNING!
Before carrying out any work: Disconnect the pump(s) and the
control unit from the mains by unscrewing and taking out the
pre-fuses, and take action to ensure that no one else can re-
connect them to the power supply.
NOTE! Work on the control unit must be carried out by qualified
electricians only!
• System does not work either in automatic or manual mode.
No mains power; check fuses and RCD switch, the operating
mode for the pump should not be set to "0".
• System does not work, "Pump motor protection" is displayed
The motor protection relay or the motor protection switch
has switched off. Check motor protection settings and set
the rated power for the pump. Acknowledge with the ac-
knowledge button and reset the motor protection switch by
hand.
• Motor protection shuts off after only a short time
Pump impeller blocked -> Clean (refer to pump manual)
Motor contactor does not switch through all phases->
Replace
Motor fault -> Call customer service personnel
• Backpressure, water rising slowly
Intake line blocked -> Clean and unblock.
• Pump delivers too little, high water alarm
Check gate valve in pressure pipe and open completely,
clean non-return valve and flush out pressure line.
• Pump thermostat
Let the pump cool down, and acknowledge with the OK but-
ton.
• Display does not show any readings
No mains power; check fuses and RCD switch, switch on the
main switch if necessary.
• Green LED does not light up
No mains power, check fuses and RCD switch, switch on
main switch if necessary, operating mode of the pump must
not be set to "0".
• Red LED lights up
The fault is shown in the display; then confirm with the ac-
knowledge button.
• No access to the menu
Password incorrect.