• AUX logic
Shows whether the auxiliary input works as an NC contact
or an NO contact
• AUX influence
Shows, what influence the auxiliary input as on the pumps
• Phase seq. monitor
Shows whether the check on the direction of rotation is
activated
• P1 current limit
Shows the current limitation that has been set for pump 1
• P2 current limit
Shows the current limitation that has been set for pump 2
• Battery voltage
Displays the voltage of the 12 V battery (only with accessory
RTC module)
• Maintenance service
Call number of the responsible customer service
• SW Version
Shows the current software version
SETTINGS
If you wish to change a parameter in this system menu, you will
be asked to enter a password (4-digit number).
NOTE! The password is set to "3197" in the factory. If the pass-
word is changed and then forgotten, the device must be re-ac-
tivated by the manufacturer' s customer service department. It
is not possible for the user to reset the system!
If more than about one minute passes in the system menu
without any entry being made, the control unit automatically
switches back to the standard display.
NOTE! Only the menu items relevant to Compli lifting systems
are described.
Level Control
The different types can be selected here. The switching levels
for the various lifting stations are already pre-set. In excep-
tional cases, however, they can be changed under this menu
item.
Timing
Max running time
Must be deactivated for Compli.
Start-up delay
In order to avoid mains disturbances in areas with many pump-
ing stations, the control unit is equipped with a variable start-
up delay. The delay time can be set from 0 to 300 seconds.
Force activation
Must be deactivated for Compli.
Alarm
In this menu all settings for the buzzer and the alarm relays are
made.
Acoustic alarm
If this function is deactivated, only the integrated alarm buzzer
is switched off.
Options: Off/on.
If a fault is acknowledged, the buzzer stops and the non-isolat-
ed relay drops out. However, the potential-free relay contacts
remain active. If the Acknowledge button is then pressed again
and the fault is no longer present, these relays are also reset to
their original position.
An external alarm acknowledgement is possible via terminals
14/15.
Alarm relay flashes
You are able to select here whether the non-isolated alarm
relay switches at one-second intervals when a fault occurs or
whether it remains on all the time: On = switches on every sec-
ond, Off = permanently on.
An alarm delay also affects this relay.
Delay alarm
NOTE! No alarm delay is available in 9V battery operation.
In order not to trigger an alarm immediately with short-term
events, a delay can be set for the switching of the alarm con-
tacts.
Setting range from 1 to 3600 seconds. A value of 0 deactivates
this function!
• Centralised alarmtime-delayed acoustic alarm and the relay
drops out with a time delay.
• High water alarm
- Analogue level detection: the relay makes contact with a
delay
ENGLISH
19