Tank assembly

Make the connection to the tank at the cold water pipe in accordance with DIN 1988.
1
Hot water (WW)
2
Circulation (ZK)
3
Heat flow (HV)
4
Boiler (HK)
5
Heat return (HR)
Note!
Prevent natural circulation of the water.
Use non-return valves or check valves with backflow preventers in the tank circuits.
When connecting the tank, observe the following points:
Observe the flow rule: "For water installations with two or more metals, then the base metals must come before the noble metals in
the direction of flow."
Stainless steel tanks must not be connected directly to galvanized or copper pipes. In this case, an intermediate insulating fitting
must be used. Red bronze, brass, plastic and stainless steel can be directly connected.
The tank must not be directly screwed to the ground because of possible transverse forces.
Note!
If a connection is not being used, it must be tightly closed and insulated.
18 — English
6
Cold water (KW)
7
Isolation valve
8
Return flow prohibiter (pipe separator)
9
Diaphragm expansion tank
10
Drain