CONSTANT PRESSURE MODE
LED1
UPM3 xx-70
UPM3 xx-50
Green
CP1
CP1
●
CP2
CP2
●
CP3
CP3
●
●
AUTOADAPT
AUTOADAPT
CP: constant pressure curve: 1, 2, or 3.
CONSTANT CURVE MODE
UPM3 xx-50
UPM3 xx-70
LED1
(m)
(m)
Green
2
4
●
3
5
●
4
6
●
5
7
●
PWM PROFILE A (HEATING)
UPM3 xx-50
UPM3 xx-70
LED1
(m)
(m)
Red
2
4
●
3
5
●
4
6
●
5
7
●
PWM PROFILE C (SOLAR)
UPM3 xx-50
UPM3 xx-70
LED1
(m)
(m)
Red
2
4
●
3
5
●
4
6
●
5
7
●
OPERATION STATUS
In performance view, the first LED is always green as long as there are no alarms.
In the settings view, it can be either green or red, indicating internal or external
control. The four yellow LEDs indicate the current power consumption (P1) as
shown in the figure and table below.
100 %
75 %
50 %
25 %
Operation area according to performance load
When the operation mode is active, all active LEDs are constantly on in order to
differentiate this mode from the select setting mode. If the circulator is stopped
by an external signal, LED 1 flashes green.
DISPLAY
INDICATION
One green LED
Standby (only externally
(flashing)
controlled)
One green LED +
Low
one yellow LED
One green LED +
Medium low
two yellow LED
One green LED +
Medium high
three yellow LED
One green LED +
High
four yellow LED
ALARM STATUS
If the circulator has detected one or more alarms, the bi-colored LED 1 switches from
green to red. When an alarm is active, the LEDs indicate the alarm type as defined in
the table below. If multiple alarms are active
at the same time, the LEDs only show the error with the highest priority. The priority is
defined by the sequence of the table. When there is no active alarm anymore, the user
interface switches back to operation mode.
LED2
LED3
LED4
LED5
yellow
yellow
yellow
yellow
●
●
●
●
●
●
●
●
LED2
LED3
LED4
LED5
yellow
yellow
yellow
yellow
●
●
●
●
●
●
●
●
●
●
●
●
LED2
LED3
LED4
LED5
yellow
yellow
yellow
yellow
●
●
●
●
●
●
●
●
LED2
LED3
LED4
LED5
yellow
yellow
yellow
yellow
●
●
●
●
●
●
●
●
PERFORMANCE IN
% OF P1 MAX
0
0-25
25-50
50-75
75-100
DISPLAY
INDICATION
One red LED
Rotor is
+ one yellow
blocked
LED(LED 5)
One red LED +
Supply voltage
one yellow LED
too low.
(LED 4)
One red LED +
Electrical error.
one yellow LED
(LED 3)
SETTINGS VIEW
You can switch from the performance view to the settings view by pressing the push
button. The LEDs indicate the actual setting. The settings view shows which mode con-
trols the circulator. No settings can be made at this stage. After 2 seconds, the display
switches back to performance view.
If LED 1 is green, it indicates operation or internal control. If LED 1 is red, it indicates
alarm or external control. LED 2 and 3 indicate the different control modes and LED 4
and 5 indicate the different curves.
LED 1
Proportional
green
pressure
Constant
green
pressure
Constant
green
curve
PWM A
red
profile
PWM B
red
profile
Curve 1
Curve 2
Curve 3
Curve 4/
AUTOADAPT
Note: ● = The LED is yellow.
HOW TO USE THE INFORMATION LEAFLET
The Circulation Unit is equipt with an information display containing a leaflet that
graphically explains what kind of application the unit is controlling. It gives you also
the possibility to write in notes and leave your business card behind.
Just remove the display glass and select the suitable information.
MAINTENANCE
The circulation unit does not require any specific maintenance under normal
conditions. Althoug it is important to annually check the entire system. Pay
specially attention to all threaded or soldered connections and the potential
occurrence of limestone sedimentation.
WARNING Switch of the electric supply before any operation. Pay attention to
the hot water contained.
SPARE PARTS
Spare parts are ordered via ESBE customer service.
In order to avoid queries and incorrect orders, all data on the name plate should
be submitted for each order.
6 (31)
PUMP
COUNTER
OPERATION
ACTION
Trying to start
Wait or deblock
again every
the shaft.
1.33 seconds.
Only
Control the
warning,pump
supply voltage.
runs.
Pump is
Control the
stopped
supply voltage
because of low
/Exchange the
supply voltage
pump.
or serious
failure.
LED 2
LED 3
LED 4
LED 5
●
●
●
●
●
●
●
●
●
●