Étude et configuration de l'unité d'entraînement
5
Installation conforme à la norme UL
5.6
Installation conforme à la norme UL
5.6.1
Field Wiring Power Terminals
5.6.2
Short Circuit Current Rating
176
Manuel produit – MOVIMOT
REMARQUE
En raison des exigences UL, le chapitre suivant est toujours en anglais et partielle-
ment en français, indépendamment de la langue de la présente documentation.
Observe the following notes for UL-compliant installation:
The devices are for use only in industrial machinery NFPA 79 applications.
For use in a Pollution Degree 1 or Pollution Degree 2 environmental only.
Use 75 °C copper wire only.
Tighten terminals to 17.7 – 21.24 in-lbs (screw connect terminals only).
Suitable for use on a circuit capable of delivering not more than 65,000 rms symmetri-
cal amperes when protected by 600  V nonsemiconductor fuses (Class CA, CB, CD,
CF, G, J, K-1, K-5, RK1, RK5, T) or when protected by 500 V minimum inverse time
circuit breakers having an interrupting rating not less than 65 kA rms symmetrical am-
peres.
®
For MOVIMOT
advanced, when used with optional Load Disconnect Switch:
Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetri-
cal amperes when protected by 600  V nonsemiconductor fuses (Class CA, CB, CD,
CF, G, J, K-1, K-5, RK1,RK5, T) or when protected by 500  V minimum inverse time
circuit breakers having an interrupting rating not less than 5 kA rms symmetrical am-
peres.
The max. voltage is limited to 500 V.
Suitable for motor group installation on a circuit capable of delivering not more than
65,000  rms symmetrical amperes when protected by, 600  V maximum nonsemicon-
ductor fuses (Class CA, CB, CD, CF, G, J, K-1, K-5, RK1, RK5, T) or when protected
by 500 V maximum inverse time circuit breakers having an interrupting rating not less
than 65 kA rms symmetrical amperes.
®
For MOVIMOT
advanced, when used with optional Load Disconnect Switch:
Suitable for motor group installation on a circuit capable of delivering not more than
5,000 rms symmetrical amperes when protected by, 600 V maximum nonsemiconduc-
tor fuses (Class CA, CB, CD, CF, G, J, K-1, K-5, RK1, RK5, T) or when protected by
500  V maximum inverse time circuit breakers having an interrupting rating not less
than 5 kA rms symmetrical amperes.
The max. voltage is limited to 500 V.
®