Deutsch
Anti-short Cycle time ON
Setting time value of minimum ON-state load.
Time value is a number of minutes.
Default value: 2 minutes
Anti-short Cycle time OFF
Setting time value of minimum OFF-state load.
Time value is a number of minutes.
Default value: 2 minutes
Pump and valve exercises
Activation or not of system exercise function.
Default value: Yes
Anti-condensation function of the installation:
only with RH sensor
When condensation is detected, air conditioning is stopped or/
and dehumidifier is activated.
Default value: Yes
EEPROM clearing
All thermostat parameters will be loaded with factory settings.
Pressing and maintaining validation key
Accessing to installer parameters
holding
button
Installer menu exit
Press validation key
screen.
|
|
Français
Nederlands
Other value: no to 5 minutes
Other value: no to 5 minutes
Other value: no
Other value: no
displays:
holding
button
to exit user menu and return to the main
|
English
Clearing
is done
releasing
button
19