4. Specifications
(1) TNU models
Model
Sound power level *
3
External static pressure
Total capacity
Indoor unit
Model
Quantity
R2 system
Indoor
W.B.
Temperature range
(Cooling)
Outdoor
D.B.
Indoor
D.B.
Temperature range
(Heating)
Outdoor
W.B.
Model
Sound power level *
3
External static pressure
Total capacity
Indoor unit
Model
Quantity
Indoor
Temperature range
(Cooling)
Outdoor
Indoor
Temperature range
(Heating)
Outdoor
*1 The maximum total capacity of indoor units operating simultaneously is 150%.
*2 To enable the high static pressure setting, set the dipswitch on the main board as follows.
SW6-5: ON
SW6-4: ON
80 Pa
SW6-4: OFF
30 Pa
*3 Cooling mode
(2) YNU models
Model
Sound power level *
3
External static pressure
Total capacity
Indoor unit
Model
Quantity
R2 system
Indoor
W.B.
Temperature range
(Cooling)
Outdoor
D.B.
Indoor
D.B.
Temperature range
(Heating)
Outdoor
W.B.
Model
Sound power level *
3
External static pressure
Total capacity
Indoor unit
Model
Quantity
Indoor
Temperature range
(Cooling)
Outdoor
Indoor
Temperature range
(Heating)
Outdoor
*1 The maximum total capacity of indoor units operating simultaneously is 150%.
*2 To enable the high static pressure setting, set the dipswitch on the main board as follows.
SW6-5: ON
SW6-4: ON
80 Pa
SW6-4: OFF
30 Pa
*3 Cooling mode
WT10508X02
PURY-HP72TNU-A1
PURY-HP96TNU-A1
75.5 dB <A>
1 to 18
+15.0°C to +24.0°C (+59.0°F to +75.0°F)
-5.0°C to +52.0°C (+23.0°F to +126.0°F)
+15.0°C to +27.0°C (+59.0°F to +81.0°F)
-30.0°C to +15.5°C (-22.0°F to +60.0°F)
PURY-HP144TSNU-A1
PURY-HP192TSNU-A1
78.5 dB <A>
1 to 36
W.B.
+15.0°C to +24.0°C (+59.0°F to +75.0°F)
D.B.
-5.0°C to +52.0°C (+23.0°F to +126.0°F)
D.B.
+15.0°C to +27.0°C (+59.0°F to +81.0°F)
W.B.
-30.0°C to +15.5°C (-22.0°F to +60.0°F)
SW6-5: OFF
60 Pa
0 Pa
PURY-HP72YNU-A1
PURY-HP96YNU-A1
75.5 dB <A>
1 to 18
+15.0°C to +24.0°C (+59.0°F to +75.0°F)
-5.0°C to +52.0°C (+23.0°F to +126.0°F)
+15.0°C to +27.0°C (+59.0°F to +81.0°F)
-30.0°C to +15.5°C (-22.0°F to +60.0°F)
PURY-HP144YSNU-A1
PURY-HP192YSNU-A1
78.5 dB <A>
1 to 36
W.B.
+15.0°C to +24.0°C (+59.0°F to +75.0°F)
D.B.
-5.0°C to +52.0°C (+23.0°F to +126.0°F)
D.B.
+15.0°C to +27.0°C (+59.0°F to +81.0°F)
W.B.
-30.0°C to +15.5°C (-22.0°F to +60.0°F)
SW6-5: OFF
60 Pa
0 Pa
PURY-HP120TNU-A1
79.0 dB <A>
84.5 dB <A>
0 Pa*
2
50% to 150%*
1
04 to 96
1 to 24
1 to 30
PURY-HP240TSNU-A1
82.0 dB <A>
87.5 dB <A>
0 Pa*
2
50% to 150%*
1
04 to 96
1 to 48
2 to 50
PURY-HP120YNU-A1
79.0 dB <A>
84.5 dB <A>
0 Pa*
2
50% to 150%*
1
04 to 96
1 to 24
1 to 30
PURY-HP240YSNU-A1
82.0 dB <A>
87.5 dB <A>
0 Pa*
2
50% to 150%*
1
04 to 96
1 to 48
2 to 50
GB-9

Publicité