3.3

3.3 Heat Pump Manager

Use the heat pump manager included in the scope of supply to
operate the air-to-water heat pump.
The heat pump manager is a convenient electronic regulation
and control device. It controls and monitors the entire heating
system on the basis of the external temperature, including do-
mestic hot water preparation and safety systems.
The customer must install the return temperature sensor and the
external temperature sensor, which are supplied with the heat
pump manager / with these instructions together with the neces-
sary fixing accessories.
The enclosed operating instructions describe the function and
use of the heat pump manager.
4

Transport

ATTENTION!
Never install the device in rooms in which there are any permanent
ignition sources.
ATTENTION!
When transporting the heat pump, ensure that it is not tilted more than
45° (in any direction).
Use a wooden pallet for transporting the heat pump to the final in-
stallation location. The basic device can be transported with a lift
truck, hand truck or by means of 3/4" pipes fed through the holes
in the base plate or frame.
The heat pump and the transport pallet are joined by four transit
bolts. These must be removed.
Before using the transport holes in the frame, it is necessary to
remove the lower side panel assemblies. This is done by loosen-
ing each of the two screws at the base and then withdrawing the
panels by unhooking them from above. Rehang the panels by
gently pushing them in an upwards direction.
Be careful not to damage any components when inserting the
pipes through the frame.
At the installation location, 8 black dust caps, which are included
in the packaging of the device, must be snapped into the trans-
port holes.
EN-4
Opening the cover
5

Installation

5.1 General

The heat pump is suited for outdoor installation. The device
should always be installed on a permanently smooth, even and
horizontal surface and must be aligned vertically. The entire
frame should lie directly on the ground to ensure a good sound-
proof seal and to prevent the water-bearing components from be-
coming too cold. If this is not the case, additional insulation
measures may be necessary. It must be possible to carry out
maintenance work without hindrance. This can be ensured by
maintaining a clearance of 1.2 m to any fixed walls.
ATTENTION!
Do not restrict or block the area around the air intake or outlet.

5.2 Condensed Water Pipe

Condensed water that forms during operation must be drained
off frost-free. To ensure proper drainage, the heat pump must be
mounted horizontally. The condensed water pipe must have a
minimum diameter of 50 mm and should be fed frost-free into a
sewer. Do not discharge the condensate directly into clearing
tanks or cesspits, as aggressive vapours or a condensed water
pipe which has not been laid in a frost-free manner could destroy
the evaporator.