LECTUS duo 3000 readers
Switch 5
Off
Off
Off
Off
Off
On
3.2.5
Resetting OSDP-key
To delete the OSDP secure channel data, execute these steps:
1.
2.
3.
4.
5.
6.
7.
Refer to
–
3.3
Troubleshooting
In case of malfunction of the reader, check these points:
–
Bosch Security Systems B.V.
Switch 6
Off
On
On
On
On
Off
Power-off the reader (e.g. by disconnecting the reader from
the AMC).
Set the reader DIP switches 5 to 8 to OFF.
Power-on the reader (e.g. by connecting the reader to the
AMC).
Wait until the reader continuously flashes the green LED
–
The green LED flashing indicates that the OSDP secure
channel data has been deleted.
Power-off the reader (e.g. by disconnecting the reader from
the AMC).
Set the correct reader DIP switch address ( Configuring the
reader (DIP switches), page 27 ).
Power-on the reader (e.g. by connecting the reader to the
AMC).
Configuring the reader (DIP switches), page 27
Is the correct power supply on the plugs of PIN 1 (8.5 VDC
to 16 VDC) and PIN 2 (0 V)?
Switch 7
Switch 8
On
On
Off
Off
Off
On
On
Off
On
On
Off
Off
Connection | en
Address
3
4
5
6
7
8
2020-10 | V02 |
31