Manual BVS 22 ATEX E 009 X
4.2
Cable entries
In the factory the cable and conductor entries are
fitted with CEAG type GHG 960 923 P... cable
glands. The tightening torques shown in Table 1
below must be adhered to.
Cable entries
Cable diameter min.
Cable diameter max.
Screw-in thread in enclo-
sure wall
Cable diameter min.
Cable diameter max.
Table 1:
Torques [Nm] for the various cable diameters
when screwing the cable glands into the wall
of the enclosure and compressing the cable
seal in the gland
4.3
Assembly of the Ex plug
The explosionproof lamps are supplied optional-
ly with an Ex plug already assembled. In cases
where the explosionproof tube lights are sup-
plied without the Ex plug, it must be ensured that
the Ex plug is assembled by an experienced
electrician in accordance with the German Indus-
trial Safety Regulations (BetrSichV) or equivalent
legislation in other countries.
4.4
Initial inspection according to IEC
60079-14, Clause 4.3, Appendix C
After installation has been completed, an initial
inspection in the form of a detailed inspection
shall be carried out.
Among other things, this initial inspection
includes checking the following:
–
the tube light is in an undamaged state
–
the tube light with EPL Gb or Db meets the
requirements relating to the installation site
–
the equipment group IIC or IIIC is correct
–
temperature class T5 is correct
–
the maximum surface temperature T95°C is
permissible
–
the degree of protection IP 66 of the
Edition August 2022
Copyright
M12
M16
M20
M25
mm
mm
mm
4.0
5.5
5.5
7.0
10.0
13.0
17.0
Nm
Nm
Nm
2.50
3.75
3.75
5.00
2.00
3.00
3.50
5.00
1.65
2.50
2.50
3.50
mm
8.0
Nm
11