Protection unit MP2.10 - MP4.10
1. Connection MP2.10 + measurement (0 283 05)
For the version with MEASURE it is necessary to set up a connection with the EMS system as described
below:
1. Connection with Power supply EMS module (item 4 149 45)
2. Connect with a max 3m cable and connector (item 4 149 07 /8/9/10) the Power supply EMS module
3. Wire the voltage plugs to the power supply lines L1 L2 L3 N (if provided)
Attention danger of
electric voltage.
Disconnect the
voltage plugs in
case of maintenance
to the device.
The length of the
cables present on
the EMS system must
not exceed 3m.
For more
information, see the
EMS guide.
86
and MP4.10 + measurement (0 283 07)
(item 4 149 45) to the DMX³ or DMX-SP 4000 electronic board.
Breaker with fuse (1 x LINE)
Interruttore con fusibile (1 x LINEA)
Connect line L1 L2 L3 x 3P
Collegare linea L1 L2 L3 x 3P
Connect line N L1 L2 L3 x 4P
Collegare linea N L1 L2 L3 x 4P
LINES
-
L2
N
-
L1
L3
L1 N L2 L3
4 149 07
4 149 10
4 149 08
4 149 09
4 149 45
max 3 m