Télécharger Imprimer la page

Tripp-Lite SmartOnline SUINT1500LCD1U Manuel D'utilisation page 23

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 63
6 Operation
6.5 Temporary Alarm Cancel Function
If the buzzer is on, press the
6.6 Battery Test
Battery tests can only be executed in On-Line Mode and ECO Mode.
1. To test the battery, press and hold the
Battery Mode and perform a 10-second battery test.
If the test result is okay, the LCD will display 'PAS' and the UPS will return to On-Line Mode or ECO Mode (according to its
original operation mode).
2. If the test result is abnormal, the LCD will display 'FAL'. The warning icon
will flash. The UPS will return to On-Line Mode or ECO Mode (according to its original operation mode).
3. If the test is canceled or interrupted, the LCD will display 'Abo', and UPS will return to On-Line Mode or ECO Mode
(according to its original operation mode).
6.7 Alarm
Condition
When the UPS is OFF and BYPASS OUTPUT is enabled
Battery Mode
Low Battery
Overload Warning
Alarm Warning
Fault
6.8 De-Rating Power
When the input voltage range is between 110 to 140V AC, the UPS load capacity will decrease to 30%.
When the input voltage range is between 140 to 180V AC, the UPS load capacity will decrease to 70%.
When the output voltage is 200V AC, the UPS load capacity will decrease to 90%.
Frequency conversion modes and frequency regulation mode will decrease to 60%.
6.9 On-Line Mode/Battery Mode/Bypass Mode Overload Cut-off
Overload Level
106-125%
126-150%
>150%
button and the buzzer will be turned off. If a new alarm occurs, the buzzer will turn on again.
button for 3 seconds. Release it after one beep. The UPS will transfer to
Action
Online Mode: Switches to Auto-Bypass within 60 seconds.
Battery Mode: Switches off completely within 60 seconds.
Bypass Mode: Switches to Auto-Bypass within 60 seconds.
Online Mode: Switches to Auto-Bypass within 10 seconds.
Battery Mode: Switches off completely within 10 seconds.
Bypass Mode: Switches to Auto-Bypass within 10 seconds.
Online Mode: Switches to Auto-Bypass within 0.2 seconds.
Battery Mode: Switches off completely within 0.2 seconds.
Bypass Mode: Switches to Auto-Bypass within 0.2 seconds.
and the no-battery/battery replacement icon
Alarm
The audible alarm beeps once every 2 minutes.
The audible alarm beeps once every 4 seconds.
The audible alarm beeps once every 0.5 second.
The audible alarm beeps once every 0.5 second.
The audible alarm beeps once every second.
The audible alarm beeps continuously.
23

Publicité

loading

Ce manuel est également adapté pour:

Smartonline suint2000lcd1uAg-03acAg-0569